Location; Appliance And Vent Clearances; Typical Installation Sequence - Lennox Elite Series Installation Instructions Manual

B-vent multi-open
Table of Contents

Advertisement

Corner - Right
(EBCR-2)
Peninsula
(EBPF-2)
Figure 2

LOCATION

In selecting the location, the aesthetic and func-
tional use of the appliance are primary concerns.
However, vent system routing to the outside
atmosphere and access to the fuel supply are
also important. Consideration should be given to
f i r e - p a r t s . c o m
traffic ways, furniture, draperies, etc., due to high
surface temperatures ( Figure 2 ). The location
should also be free of electrical, plumbing or
other heating/air conditioning ducting.
The appliance should be mounted on a fully
supported base extending the full width and
depth of the unit. The appliance may be located
on or near conventional construction materi-
als. However, if installed on combustible mate-
rials, such as carpeting, vinyl tile, etc., a metal
or wood barrier covering the entire bottom
surface must be used.

APPLIANCE AND VENT CLEARANCES

The appliance is approved with zero clearance to
combustible materials on all sides (as detailed in
Table 2) , with the following exception: When the
unit is installed with one side flush with a wall,
the wall on the other side of the unit must not
extend beyond the front edge of the unit. In
addition, when the unit is installed in the middle
of a room, the side walls surrounding the unit
must not extend beyond the front or rear edge
of the unit. See Figure 2 .
Vertical Vent Termination Clearances
Gas Vent Rule – Gas vent caps are not permit-
ted within 8 feet (2.4 mm) of a vertical wall or
similar obstruction. Gas vent caps that are
located 8' or more from a portion of a building
which extends at an angle greater than 45°
upward from the horizontal may terminate in
accordance with (Figure 3 ) , provided that in
no case shall any discharge opening on the
cap be less than 2' (610 mm) horizontally from
the roof surface (National Fuel Gas Code ANSI
Z223.1 (NFPA 54) 7.6.2) (CAN/CGA B149).
4
TYPICAL LOCATIONS
*When See-Through (EBST-2) is
Corner - Left
installed with one side flush
with a wall,opposite wall must
(EBCL-2)
n o t e x t e n d b e y o n d e i t h e r
viewing side of the fireplace.
**See-Through
(EBST-2)
Bay
(EBBAY)
**
installed in the middle of a room,
do not extend side walls beyond
*See-Through (EBST-2) -
either viewing side of the fireplace.
one side flush with a wall
B
A
C
K
S
D I
E
S
T
O
P
S
P
A
C
E
L F
O
O
R
F
o r
m
B
t o
o t
f o
U
n
t i
o t
C
e
i l i
g n
V
E
N
T
S
E
R
V
E I
W
N I
G
S
D I
E
S
-
F (
R
O
N
, T
B
A
O
R
S
D I
) E
Table 2
These instructions should be used as a guide-
line and do not supersede local codes in any
way.
Multiple Terminations – These appliances may
vent adjacent to and at the same level with any
other gas appliances (including direct-vent ap-
pliances) provided that there is at least 2 ft.
(0.6m) between the proximal edges of the vent
caps. These appliances may be vented adja-
cent to a chimney vent servicing a solid fuel
fireplace provided the B-vent cap is at least 2 ft.
(0.6m) away from the nearest point of the
chimney opening.
Note: Venting terminals shall not be recessed
into a wall or siding.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
When See-Through (EBST-2) is
1
2 /
n i
( .
3 1
m
m
)
0
. n i
0 (
m
m
)
s
a p
e c
s r
1
2 /
n i
( .
3 1
m
m
)
0
. n i
0 (
m
m
)
s
a p
e c
s r
R
S
0
. n i
0 (
m
m
)
0
. n i
0 (
m
m
)
m
4 6
n i
( .
6 1
6 2
m
m
)
1
n i
( .
5 2
4 .
m
m
)
V
C I
E
C
E L
A
R
A
N
C
E
S
3
e F
. t e
0 (
9 .
m
t e
r e
) s
C
K
12
Roof Pitch is X/12
Minimum Height from Roof
to Lowest Discharge Opening
Minimum Height
from Roof to Lowest
Roof Slope
Discharge Opening
Feet
Flat to 6/12
1' 0"
Over 7/12 to 9/12
2' 0"
Over 10/12 to 12/12
4' 0"
Over 13/12 to 16/12
6' 0"
Over 17/12 to 21/12
8' 0"
Figure 3

TYPICAL INSTALLATION SEQUENCE

The typical sequence of installation follows,
however, each installation is unique resulting
in variations to those described.
See the page numbers references in the fol-
lowing steps for detailed procedures.
Step 1. (page 5) Construct the appliance
framing. Position the appliance within the
framing and secure with nailing brackets.
Step 2. (page 5) Route gas supply line to
appliance location.
Step 3. (page 5) Install the vent system
and exterior termination.
Step 4. (page 10) Field Wiring
a. Millivolt Appliances – The operating con-
trol switch is factory installed.
b. Electronic Appliances – Connect 120 Vac
electrical power to the appliance receptacle.
Step 5. (page 11) Make connection to gas
supply.
Step 6. (page 12) Outside Air Kit Installation
Step 7. (page 13) Install the log set, ver-
miculite and ceramic fiber chunks.
Step 8. (page 13) Checkout appliance op-
eration.
Step 9. (page 13) Install glass enclosure
panels.
Step 10. (page 14) Burner Adjustment.
Step 11. (page 14) Spillage Test and Safety
Limit Switch Operation.
Step 12. (page 15) Install the hoods.
X
Meters
0.3
0.6
1.2
1.8
2.4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents