top of the slide slot. Both pilot and main burner should go out.
While cooling the ceramic fuel effects may make some crackling noises. This is quite
normal.
3. Check that the control linkage bar does not interfere with the appliance cable
retention nuts or wires.
14. SPILLAGE & FLAME SUPERVISION CHECKS
14.1 Check for spillage.
A spillage check must be made before leaving the installed appliance with the
customer. Make this with all the ceramic fuel effect pieces in position.
1. Close all doors and windows in the room containing the appliance.
2. Light the appliance and turn the control knob to "HIGH".
3. Leave the appliance on for five minutes.
4. Place the smoke match into the appliance canopy (See figure 32).
5. The installation is satisfactory if the smoke is
drawn into the appliance. If the smoke is not drawn
into the appliance, leave the appliance alight at the
maximum setting for a further ten minutes and then
repeat the test. If smoke is still not drawn into the
appliance, inspect the sealing to the fireplace
surround. If the sealing is satisfactory but the
appliance is installed with the flue restrictor (See
section 8.2), remove the restrictor, reseal the
appliance and retest. If smoke is still not drawn into
the appliance, disconnect the appliance and seek
expert advice.
6. If the above test is satisfactory, open all internal
Figure 32. Spillage check
connecting doors, hatches, etc., in the room. Keep
all doors and windows that open to the outside of the
building closed. Recheck for spillage as above. If an extractor fan is installed in the
same room as the appliance or a connecting room, check that spillage does not occur
with the fan operating and all doors and other openings between the fan and the
appliance open. If the smoke is drawn into the appliance, continue with the installation.
If the test is not satisfactory, disconnect the appliance and advise the customer of the
cause of failure.