Honeywell 7000 Product Data page 13

Solid state alarm system
Table of Contents

Advertisement

Type
Perimeter
A burglary circuit that instantly alarms on cross or break when violated.
Entry/Exit 1
A burglary circuit that signals a warning for time period 1 before alarming.
Entry/Exit 2
A burglary circuit that signals a warning for time period 2 before alarming.
Interior
A burglary circuit that is ignored during the exit and entry delay periods.
Interior Delay
A burglary circuit that signals a warning for time period 2 when violated and is ignored during the
normal exit and entry delay periods.
Tamper
A burglary circuit that is always on. Violation of this point will be reported but the local audible alarm
can be optioned to be silenced.
Police
A burglary alarm that instantly alarms on cross or break when violated. The audible alarm is
selectable separately.
Fire
A fire circuit that instantly alarms on cross and signals a trouble on break.
Medical/Special
A circuit that instantly alarms with a separate audible sound.
Equipment Supervisory A circuit that instantly alarms with a separate audible sound.
Strategy (Mode):
An input that invokes a specified security mode.
Smart
A burglary point or zone that can be part of the complete security as well as operated separately by
Special Protection Modes. Used for protecting an isolated door (to let pets out, for example), as well
as protection for the home office, bar, gun rack, workshop, etc. This point alarms instantly when
occupants are away and sounds a warning for time period 2 when persons are at home.
Pool
Violation of the point causes the keypad audible to sound throughout the house for 30 seconds
when occupants are home and the keypads, bell or siren to sound for 30 seconds when occupants
are away. Requires a separate device to be installed to delay the audible on entry or briefly bypass
the audible on exit by an adult. Available from Safeguard Innovations: (612) 784-7786.
Fire Circuits
The Honeywell 7000 System directly supports certain
specified two-wire fire detectors. Four-wire detectors require
special wiring and programming arrangements for resetting
smoke detectors.
Two-Wire Smoke Detector Circuit
The Honeywell 7000 System directly supports one two-wire
fire circuit (loop 8 on the control panel). Use the following
approved smoke detector models and refer Fire Marshals to
the compatibility ID shown in Table 3. The compatability ID for
the Honeywell 7000 System is 7K8.
Table 3. Two-wire smoke detectors and compatibility ID.
Manufacturer
Model
Sentrol
429A, 429AT
Detection
DS250, DS250TH,
Systems
DS50HD Detectors
MB2W, MB2WL Bases
Two-Wire Fire Circuit Installation
1. Install smoke and heat detectors in accordance with
manufacturer instructions.
HONEYWELL 7000 SOLID STATE ALARM SYSTEM
Table 2. Input loop point types.
Description
2. Use UL-listed 18 AWG energy limited cable (Signal
3. Attach the 5.1 Kilohm, 1/4 watt EOLR (provided) at the
4. Wire detectors as shown in Fig. 15.
Compatibility ID
S10A
B
A
Fig. 15. Wiring diagram for two-wire smoke detectors.
13
Cable Co. No. 98804, for example) to wire a maximum
of 10 two-wire smoke detectors within 200 feet of the
control panel.
last smoke detector.
TB1
15
16
+
SMOKE
DETECTOR
+
+
MAXIMUM OF 10
SMOKE
2 WIRE
DETECTOR
SMOKE DETECTORS
+
EOLR
5.1 K
5%
1.4W
M10900
69-1192—1