HONEYWELL 7000 SOLID STATE ALARM SYSTEM
IMPORTANT
The following limits must not be exceeded:
1.
Maximum normal total current: 1.05A.
2.
Maximum alarm current on TB1-18 (HORN):
950 mA.
3.
Maximum alarm current on TB1-17 (AUX):
100 mA.
4.
Maximum number of batteries: 4 (28 AH total
capacity).
5.
Total current drawn from TB1-20 (+13.8 Vdc):
1.0A.
Minimum System
The minimum UL system is:
1. One control panel.
2. One keypad.
3. Up to 10 two-wire smoke detectors (or equivalent four-
wire smoke detectors).
4. One siren (950 mA model).
Table 8 summarizes the power calculations for this system.
Using the battery calculation formula:
(0.210A X 24 hours) + (1.185A X 1/15 hour) + 10% =
5.64 AH.
Device
Control Panel with 8 Points
Keypad
PEM
RFEM
5881 RF Receiver
Horn
Smoke Detectors
Miscellaneous/AUX Devices
TOTALS
Standby
Configuration
Battery
No.
Hours
1
24
2
24
3
24
4
24
5
24
6
24
*7
4
*8
4
*9
4
*10
4
*These configurations are for non-fire applications.
69-1192—1
Table 8. Power calculations.
Normal Current
Quantity
Each
1
90
1
120
0
60
0
60
0
50
1
0
10
0
0
0
Table 9. Sample system configurations.
RF
Number of
Total
RFEM +
Batteries
AH
RCVR
1
7
No
1
8
No
1
8
Yes
2
14
No
2
14
Yes
2
14
Yes
1
7
Yes
1
7
Yes
1
7
No
1
7
No
This configuration requires one 7AH battery.
Maximum System
The maximum system is any configuration that requires 28AH
of standby battery power.
Sample Configurations
Table 9 lists sample configurations. Any of these
configurations can be downsized (less modules or
components) and still meet the battery standby times for that
configuration. Installation per these guidelines will meet the
California State Fire Marshal (CFSM) 24-hour battery backup
requirement.
Earth Wire Grounding
An earth ground can be a cold water pipe, a ground rod, the
metal framework of a building, or the reinforcing rod (concrete
rebar) of a building as shown in Fig 20. The third wire ground
in building electrical wiring should not be used as earth
ground as it is difficult to establish reliability as an earth
ground.
Normal Current
Total
90
120
0
0
0
0
0
0
210
2-Wire Smoke
Detectors
PEM
Keypad
(Maximum)
1
1
10
0
2
10
0
1
10
1
4
10
0
3
10
2
2
10
4
5
None
0
7
None
0
8
None
4
6
None
18
Alarm Current
Alarm Current
Each
Total
90
90
120
120
60
60
50
950
950
25
25
0
1185
Aux.
Maximum
Power
Normal
(mA)
Current (mA)
Current (mA)
19
263
27
301
7
301
13
527
53
527
23
527
10
900
10
840
0
810
0
870
0
0
0
0
Maximum
Alarm
1455
1398
1405
1865
1870
1870
2000
2000
2000
2000