Carrier 42C Series Product Data page 24

Fan coil air conditioners 60 hz 150 to 2000 cfm
Table of Contents

Advertisement

Application data (cont)
SYMBOL/SKETCH
LEGEND
Cv — Coefficient of Velocity
DX — Direct Expansion
ETO — Engineering to Order
*Check all system component pressure ratings (coils, values, pumps,
etc.) with manufacturer and any applicable local or national piping
codes prior to specifying system pressure rating.
24
PIPING COMPONENTS
DESCRIPTION
MANUAL AIR VENT: Threaded brass needle
valve with screwdriver slot for adjustment.
Application — Body brazed into high point of
heating and cooling coils for bleeding air from
coil. Standard item on all hydronic coils (not
used on steam or DX coils). Should not be
used in lieu of main system air vents.
AUTOMATIC AIR VENT: Nickel plated brass
valve, fiber-disc type, with positive shut-off ball-
check and quick vent feature via knurled vent
screw.
Application — Optional replacement for man-
ual air vent. Automatically passes minute
quantities of air through the fiber discs which
expand upon contact with water, completely
sealing the valve. As air accumulates, the fiber
discs dry and shrink, repeating the cycle. Not
recommended for removing large quantities of
air encountered during initial start-up or subse-
quent draining and refilling. Should not be
used in lieu of main system air vents.
SWAGE: Copper tube end expanded to accept
a copper tube of the same size for factory or
field brazing.
Application — Used where possible for all tub-
ing joints for best joint integrity.
UNION: Combination wrought copper/cast
brass union assembly, solder by solder.
Application — Used for quick connect (and dis-
connect) of valve package components to min-
imize field labor and facilitate servicing of unit.
INSERTION TEST PORT: Brass body valve
for acceptance of test probe (up to
diameter).
Application — Installed on one (or both) sides
of the coil to allow for temperature or pressure
sensing. Used for close tolerance water bal-
ancing and service analysis.
PRESSURE TEST PORT: Brass body
vice access fitting with removable depressor
type core.
Application — Installed on both sides of the
coil to allow for pressure sensing. Attach pres-
sure gages to facilitate close tolerance water
balancing.
CIRCUIT SETTER: Variable water flow balanc-
ing valve with manual adjustment knob,
pointer, percent-open scale, memory stop and
integral pressure read-out ports.
Application — Used for close tolerance water
flow balancing. Positive shut-off ball valve fea-
ture allows usage as combination balancing
and shut-off valve.
C
FACTOR
V
1
/
2
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
1
/
in.
8
N/A
N/A
1
/
ser-
4
N/A
N/A
2.12
RATING*
3
/
PSI
F
4
400
100
125
240
300
200
300
200
250
250
400
210
3.9
300
250
STEAM
USE
NO
NO
YES
YES
NO
NO
NO

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents