Category 2 - System Settings; Additional Installation Information; Binding / Rebinding Procedure; Multi-Zone System - Honeywell CM727 Installation Manual

Wireless programmable room thermostat & bdr91 relay box
Hide thumbs Also See for CM727:
Table of Contents

Advertisement

4.5.2 Category 2 - System Settings

Parameter
Parameter
No.
Category 2 Parameters – System Settings (press the
Minimum boiler
1:Ot
ON time
Cycle Rate
2:Cr
Pump Exercise
5:PE
System
6:Sn
Synchronisation
Loss of
7:LC
Communications
Instruction
Note
1) Remember to always press the green
Up setting. To exit the Installer Mode press the AUTO or MAN button.

5) Additional Installation Information

5.1 Binding / Rebinding Procedure

The binding operation described below is required if:
• Any of the system components (room thermostat or relay box) are replaced.
• The relay box has incorrect or no binding data stored (e.g. when pre-bound system pack components
have been mismatched).
NOTE: During the binding procedure keep approximately 1m distance between the room thermostat and
the relay box.
To bind/rebind:
1. Press and hold the relay box push button for 15 seconds to reset any previously stored data. After 15
seconds the red LED will change to flashing 0.1sec on/0.9sec off.
NOTE: After 5 seconds the red LED will start to flash 0.5sec on/0.5sec off, but continue to hold the
button).
2. Release the push button.
3. Press and hold the relay box push button for 5 seconds to enter the binding mode. The Red LED will
start flashing at 0.5sec on/0.5sec off to confirm the binding mode has been entered.
4. Press the OFF button on the room thermostat. Then press the
the
button. The unit will display InSt and 'CONTROL BINDING'.
5. Press the green
button to send the binding signal out to the relay box. The red LED is switched off
to confirm successful binding operation. If the red LED still flashes push the button again until binding
is successful.
6. Now go to Section 2) Installing the CM700 Wireless System to setup the system.
10
Factory Default Setting
button to access this category)
Display
Description
1
1 minute minimum
ON time
6
6 cycles per hour
(cph)
0
Pump exercise
disabled
0
Standard operation
of the Room Unit
0
Relay Off
button to confirm that you want to store your new Installer Set-
CM700 Wireless - Programmable Room Thermostat
Optional Setting
Display
Description
2 to 5
Selection of 2, 3, 4 or 5 minutes
minimum ON time
3,9 or
Selection of 3, 9 or 12 cph
12
1
Pump exercise enabled
1
Room unit configured as
Synchroniser
1
Relay 20% on / 80% off
and
buttons together along with