2.3
Transmitter location
Pressure models
Process
Gases
Liquids
2.4
Bracket mounting
Attach bracket to pipe
Figure 7 shows some commonly used bracket and pipe orientations. Not all possibilities are shown; you
can use any bracket (flat or angle) and orientation (parallel or transverse) to get the desired transmitter
positioning.
Position bracket on 2-inch (50.8 mm) pipe and install "U" bolt around pipe and through holes in bracket.
Secure with nuts and lockwashers provided.
Revision 3
8/8/07
Suggested location
Above the gas line
•
Below but close to the
elevation of the process
connection.
•
Level with or above the
process connection.
A
C
E
Figure 7 Common bracket orientations
OneWireless XYR 6000 Transmitters Quick Start Guide
2. Transmitter Mounting
2.3. Transmitter location
Explanation
The condensate drains away from the
transmitter.
•
This minimizes the static head
effect of the condensate.
•
This requires a siphon to protect
the transmitter from process
steam. The siphon retains water as
a "fill fluid."
B
D
F
9