System Set Up Menu - Neptronic SKG3 Series Installation Instructions Manual

Gas fired humidifier
Table of Contents

Advertisement

Display
SYSTEM SETUP
300
Service Timer:
Service Timer
Selection of delay between Service alarms.
1000 Hrs
Value is indicated in Hours.
SYSTEM SETUP
Auto drain Delay:
301
Auto Drain Delay
Selection of Delay between automatic flush of evaporation
4 Hrs
chamber.
Value is indicated in Hours.
SYSTEM SETUP
302
No Demand Delay:
No Demand Delay
Selection of Delay when No Demand.
72 Hrs
Value is indicated in Hours.
SYSTEM SETUP
Fan ON Delay:
303
Fan ON Delay
Selection of Delay to keep Fan ON when No humidity
10 Min
demand.
Value is indicated in Minutes.
Holding Temperature:
SYSTEM SETUP
304
Selection of Evaporation chamber temperature between
Holding Temperature
humidity demands. If enable, combustion will be ordered to
OFF
maintain a specific water temperature
Value is indicated in
Anti Freeze Temperature:
Selection of Evaporation chamber anti freeze temperature.
SYSTEM SETUP
305
If enable, combustion will be ordered to maintain water
Anti Freeze Temper.
temperature between 7 and 12°C
OFF
This Screen is not available for weather proof enclosure
option humidifier.
Value is indicated in
Water Temperature Offset:
Selection of Evaporation chamber temperature offset for
SYSTEM SETUP
306
each module, to adjust reading of the water temperature
Water Temp. Offset
probe to proper temperature.
H1: 0°C
H2: 0°C
When producing steam, evaporation chamber water
H3: 1°C
temperature probe should indicate 100
H4: -1°C
Value is indicated in
Water Level Offset:
SYSTEM SETUP
307
Selection of Evaporation chamber water level offset for
Water Level Offset
each module, to adjust reading of the water level probe to
H1: 0%
H2: -1%
the proper level.
H3: 2%
H4: 0%
Value is indicated in
Chimney Temperature Offset:
SYSTEM SETUP
308
Selection of Chimney temperature offset for each module,
Chimney Temp. Offset
to adjust reading of the chimney temperature probe to
H1: 0°C
H2: 1°C
proper temperature.
H3: -1°C
H4: 0°C
Value is indicated in
Description
˚C, when enable.
˚C, when enable.
˚F)
˚C (212
˚C.
%.
˚C.
41
SKG3 Steam Humidifier

System Set Up Menu

Values
From 400 to 3000 Hrs
Increment: 100 Hrs
Default:1000 Hrs
From 1 to 24 Hrs
Increment: 1 Hr
Default:8 Hrs
From 1 to 250 Hrs
Increment: 1 Hrs
Default:72 Hrs
From 3 to 30 Min.
Increment: 1 Min.
Default:10 Min.
From 50 to 90˚C or
OFF
Increment: 5˚C
Default: OFF
From 7 to 12˚C or OFF
Increment: 1˚C
Default: OFF
From -10 to 10˚C
Increment: 1˚C
Default: 0˚C
.
From -10 to 10%
Increment: 1%
Default: 0%
From -10 to 10˚C
Increment: 1˚C
Default: 0˚C