Operation Display - Neptronic SKG3 Series Installation Instructions Manual

Gas fired humidifier
Table of Contents

Advertisement

Operation scrolling
messages on
display
Scrolled message
ROOM SETPOINT
ROOM HUMIDITY
HI-LIMIT SETPOINT
WATER LEVEL
WATER
TEMPERATURE
AIR FLOW IS OPEN
DRAIN CYCLE
END OF SEASON
DELAY IS OVER
! ! ! INPUT SUPPLY
TOO LOW
! ! ! HI-LIMIT CUT OUT
! ! ! INTERLOCK OPEN
! ! ! CLEANING
REQUIRED
CALL SERVICE
PEOPLE
! ! ! SERVICE UNIT
NOW
! ! ! CRITICAL ALARM
PRESENT SEE MENU
! ! ! NON-CRITICAL
ALARM PRESENT
SEE MENU
During normal operation the following display will indicate main information about the
system:
DEMAND: 100%
OUTPUT: 100%
ROOM HUMIDITY
30%RH
Current room set point in % RH.
Current room humidity reading in % RH.
Current Hi Limit Duct set point in % RH.
Current water level reading in evaporation chamber for each module in %.
Current water temperature reading in evaporation chamber for each module in ˚C.
No air flow is detected in the duct. Humidifier is stopped.
Drain cycle in process
72 hours without humidity demand. Evaporation chamber(s) of the humidifier has been flushed
of the remaining water in order to prevent growth of bacteria. Upon new humidity demand
evaporation chamber(s) will fill up with fresh water and produce steam.
Voltage supply is below the minimum value. Humidifier is stopped.
Hi limit RH% is above Hi limit set point. Humidifier is stopped.
Interlock safety is open. Humidifier is stopped.
Nb of hours to service will be reached within 50 hours. Humidifier continue to operate but will
stop for service soon.
Nb of hours to service has been reached. Humidifier is stopped. It is time to service the
Humidifier.
Abnormal critical situation has been detected. Humidifier is stopped. Go to Alarm menu for
detail.
Abnormal non critical situation has been detected. Humidifier may continue to operate. Go to
Alarm menu for detail.
SKG3 Steam Humidifier
Description
37

Operation display