Heating – Modulating Valve Piping

Hot Water (or 2-pipe CW/HW) Modulating Valve Piping

When piping the modulating valve, refer to the arrows on the modulating
valve body to determine the direction of flow. The valve should be
installed so that there is a 2" (51mm) minimum clearance to remove the
actuator form the valve body. Provide unions for removal of unit coil and/
or control valve as a future service consideration. Hot water connections
may be same end as cooling coil connections, but are recommended
to be opposite end to facilitate piping. When using AAF MicroTech II
controls, they must be opposite end. The modulating valve accessory
must be field installed on the unit for which it was selected.
CAUTION
Refer to the arrows on the modulating valve body to determine
the direction of flow. If the valve is mounted improperly, the unit
will not operate properly and damage to the valve may result.
2-way Modulating, Normally Open, Hot Water
or 2-pipe CW/HW Valve Piping (typical)
The 2-way Modulating hot water (or 2-pipe CW/HW) valve is furnished
normally open to the coil. When the valve is de-energized (off) there
is full flow through the coil. Energizing the valve reduces the volume
of water flow in a modulating fashion.
Figure 78 - 2-way Modulating Valve Control, Normally Open, Hot
Water or 2-pipe CW/HW Piping
Return
Balancing and Shutoff Valve
2-way
Modulating
Valve
S5 Sensor
(2-pipe CW/HW Units Only)
Shutoff Valve
Supply
IM 817-4
Unit Coil
Return
Supply
Unions
3-way Modulating, Normally Open, Hot
Water or 2-pipe CW/HW Valve Piping (typical)
The 3-way Modulating hot water (or 2-pipe CW/HW) valve is furnished
normally open to the coil. When the valve is de-energized (off) there
is full flow through the coil. Energizing the valve allows a varying
amount of water to bypass the coil.
Figure 79 - 3-way Modulating Valve Control
Return
N.C.
Balancing Valve
S5 Sensor
(2-pipe CW/HW Units Only)
Supply
Figure 80 - 3-way Modulating Valve Control
(Piping Outside Unit End Compartment)
15
4
5
7
6
See page 25 for number designation descriptions.
Balancing and Shutoff Valve
3-way
Modulating
Valve
Union
Common
N.O.
Return
Supply
Union
Shutoff Valve
11
2
15
3
15
S5 Sensor
Page 27 of 60
Unit Coil