Regency F5100 Owners & Installation Manual page 12

Freestanding woodstove
Table of Contents

Advertisement

INSTALLATION
FLOOR PROTECTION
A combustible fl oor must be protected by non-combustible
material (like tile, concrete board, or certifi ed to UL-1618 or
as defi ned by local codes) extending beneath the heater and
a minimum of 8" (203mm) from each side and minimum 16"
(406mm) from the front face of the stove and minimum 6"
(or the rear clearance to combustibles whichever is smaller)
from the rear of the stove.
When installed with horizontal venting, non-combustible fl oor
protection must beneath the fl ue pipe and extend 2" (51mm)
beyond each side.
Minimum Overall Width (X) of Floor
Protector for all installations:
Stove
F5100
12
45" (1143 mm)
Unit
F5100
USA
Canada
The rear clearance to combustibles is less than 6" (for corner installations the rear corners may
be angled to take advantage of the closer clearances.
8
NOTE: In Canada, fl oor protection must extend 18" (450mm) to the front
and 8" (203mm) to each side and back of the stove.
Minimum Overall Depth (Y) of Floor Protector
Residential
Close Clearance
Y
Z
49-1/8"
8"
53-1/8"
8"
8
8
Mobile Home
Close Clearance
Y
Z
Y
49-1/8"
8"
49-1/8"
53-1/8"
8"
53-1/8"
F5100 Regency Freestanding Woodstove
8
Alcove
Z
8"
8"

Advertisement

Table of Contents
loading

This manual is also suitable for:

F3500

Table of Contents