4. Operation
Power output stop delay time setting (setting switches 5 and 6 ) ... Factory-
shipped setting: OFF and OFF
The UPS delays the power supply output stop timing.
If the user sets "switch 5: ON, switch 6: ON", the UPS does not stop the output, even if the backup stop (BS) is
valid.
<Note>
The remote ON/OFF signal is not related to this setting.
When the remote ON/OFF signal is "closed", the UPS stops the output immediately.
ON
1
Setting switch 5 Setting switch 6
OFF
ON
OFF
ON
AC input
ON
OFF
BS signal
ON
OFF
UPS output
ON
OFF
This timing is 10 ms or 10 sec.
Timing corresponds to the settings
for switch 7 .
2
3
4
5
6
7
8
Power output stop
delay time
OFF
0 second
OFF
60 seconds
ON
120 seconds
Does not stop
ON
power output
Power supply output stop delay timing
This delay corresponds to the settings
for switch 5 and switch 6 .
34