Release Valve Control; Fixed-Speed Compressor High Pressure Release Control - Toshiba HFCR407C Service Manual

Multi splite type system hfc r407c
Hide thumbs Also See for HFCR407C:
Table of Contents

Advertisement

Item
7. Release valve (1) SV2 gas balance control
control
11
8. Fixed-speed
compressor
high pressure slave outdoor unit.
release control
Outline of control
Outdoor unit
Operation explanation and applied data, etc.
This control is executed to balance the gas by opening SV2 while the compressor is
off, in order to decrease the activation load in the next compressor-ON time. This
control is individually executed by the master outdoor unit and each slave outdoor
unit.
1)
Control conditions
When the compressor is switched from ON to OFF operation.
2)
Contents of control
• The control point is exchanged by ΔP
(Pd pressure - Ps pressure) immediately before the compressor stops.
• When ΔP ≥ P1, SV2 is opened. After SV2 has been opened, SV2 is turned off
when ΔP< P2.
• When ΔP< P1, SV2 is closed.
<Table 7a>
Pd pressure
Cooling
control point
Master outdoor
P1, P2
compressor OFF
P1
In case of master
13
In case of slave
13
(2) SV2 low pressure release control
This control is to prevent pressure drop during transient operation. This control is
individually executed by the master outdoor unit and each slave outdoor unit. This
control is executed as necessary except during stop time and thermostat-OFF time.
1)
Contents of control
• SV2 is opened when Ps pressure>0.8 kgf/cm
• SV2 is closed when Ps pressure>1.2 kgf/cm
(3) SV2 compressor case bypass control
This control is to prevent oil dilution. This control is individually executed by the
master outdoor unit and each slave outdoor unit.
This control is executed during compressor-ON (except during oil level detection
control).
1)
Contents of control
SV2 is opened when the following conditions are satisfied.
• Compressor status changes from OFF to ON.
• Oil recovery control is performed in cooling mode.
• SV2 is opened when TK3 sensor detects 2°C or lower, and closed when TK3
sensor detects 5°C or higher temperature during compressor-ON time.
• No. of outdoor fan waves is 3 waves or less during cooling compressor-ON.
This control is to stop the fixed-speed compressor of each outdoor unit according to Pd
pressure value. This control is individually executed by the master outdoor unit and each
1)
Contents of control
• The fixed-speed compressor stops when Pd pressure is over P1 (Table 7a).
• Sets the fixed-speed compressor reactivation time for 10 minutes, and the
control finishes.
Master outdoor
compressor ON
P2
P1
P2
11
-
-
11
5
4
G
2
2
G
58
Remarks
kgf/cm
2
G
• No. 2 compressor
stops with Pd ≥,
P1 = 26.5 kgf/cm
2
G
• No. 1 compressor
stops with Pd ≥,
P1 = 27.5 kgf/cm
G