NOTE 1:

Criteria for indoor air inlet/outlet temperature difference

After operation for a minimum of 30 minutes in "COOL" mode, if temp. difference between the air inlet and air
outlet of the indoor unit is 8°C or more – operation is normal.
(In Max. Hz operation)
The difference in temperature between the air inlet and air outlet decreases when the total number of
indoor units connected, exceeds 100% of the system capacity, or when the pipe length exceeds
specification.
NOTE 2:

Criteria of operation current value

In cooling operation, when the current is within ± 15% of the specified current value, the system is operating
normally.
(COOL Max. Hz operation)
The current value differs as described below according to the operation conditions.
Greater than the specified current
(1) Temp. in indoor/outdoor is high.
(2) Radiation of outdoor unit is bad.
Less than the specified current
(1) Temp. in indoor/outdoor is low.
(2) Gas leakage. (Insufficient refrigerant amount)
NOTE 3:

Criteria of operation pressure

COOL/HEAT
NOTE: Measurement taken 15 minutes after operation start (db = Dry bulb temp. °C).
Trial operation
Procedure and summary of trial operation
High pressure 16 to 22 kgf/cm
Low pressure 3.5 to 5.5 kgf/cm
G
Indoor 18 to 32 °C db
2
2
G
Outdoor 25 to 35 °C db