[ II Restrictions ]
2. Restrictions on pipe length
(1) System that requires 16 BC controller ports or fewer <System with only the main BC controller or standard BC con-
troller>
Outdoor unit
H
H'
h1
Length
Total pipe length
Total pipe length from the outdoor unit
to the farthest indoor unit
Between outdoor unit and BC control-
ler
Between BC controller and indoor unit
Height
difference Between indoor
and outdoor units
Between indoor unit and BC controller
Between indoor units
*1. When the capacity of the connected indoor units is P200 or above, use the figures in the parentheses as a reference.
1) To connect the P100 through P140 models of indoor units, use an optional junction pipe kit (Model: CMY-R160-J1) and merge
the two ports before connecting them. (In that case, set DIP SW4-6 on the BC controller to ON.)
It is also possible to connect the P100 through P140 models of units to a port, although the cooling performance will somewhat
decrease. (In that case, set DIP SW4-6 on the BC controller to OFF.)
(The factory setting for DIP SW4-6 is OFF. )
2) Do not connect the P200 or P250 models of indoor units and other models of indoor units at the same port.
3) All the units that are connected to the same ports can only be operated in the same operation mode (cooling/heating).
4) Do not use the existing Y-shaped twinning pipe.
Make sure to change the twinning pipe to the one for use with R410A.
If the existing twinning pipe is T-shaped, there is no need to change.
HWE10140
A
BC controller
Reducer (P15 - P50 models)
(Supplied with the BC Controller)
a
Junction pipe
(CMY-R160-J1)
Indoor
(P15 - P80 models)
Operation
Outdoor unit
above indoor unit
Outdoor unit be-
low indoor unit
*Use a main BC controller when connecting the outdoor units of
P400 model or above.
Branch joint
B
b
c
Indoor
Indoor
Maximum of 3 units per port
(P100 - P250 models)
Total capacity of P80 or below
Pipe sections
A+B+a+b+c+d
A+B+d
A
B+d
H
H'
h1
h2
- 50 -
Indoor
d
h2
Allowable length of pipes
220 [721] or less
100 [328] or less
(Equivalent length 125 [410] or less)
70 [229] or less
30 [98] or less
50 [164] or less
40 [131] or less
15[49](10[32]) or less
15[49](10[32]) or less
Unit: m [ft]