[ IX Troubleshooting ]
[3]
(1)
Check whether
the inverter is
damaged.
(No load)
(2)
(3)
[4]
Put the outdoor unit into oper-
Check whether
ation.
the inverter is
Check the inverter output volt-
damaged.
age after the inverter output
(During com-
frequency has stabilized.
pressor opera-
tion)
[5]
Remove the wire for the out-
Check the fan
door fan motor, and check the
motor ground
fan motor megger and the
fault or the
winding resistance.
winding.
HWE10140
Items to be checked
Disconnect the inverter
output wire from the ter-
minals of the INV board
(SC-U, SC-V, SC-W).
Disconnect the short-cir-
cuit connector from CN6
on the INV board.
Put the outdoor unit into
operation.
Check the inverter output
voltage after the inverter
output frequency has sta-
bilized.
Phenomena
1)
Inverter-related problems are de-
tected.
2)
Inverter voltage is not output at the
terminals (SC-U, SC-V, and SC-W)
3)
There is an voltage imbalance be-
tween the wires.
Greater than 5% imbalance or 5V
4)
There is no voltage imbalance be-
tween the wires.
1)
Overcurrent-related problems oc-
cur immediately after compressor
startup.
Error code : 4250
Detail code : 101, 106, 107
2)
There is a voltage imbalance be-
tween the wires after the inverter
output voltage is stabilized.
Greater than the larger of the fol-
lowing values: imbalance of 5% or
5V
1)
Fan motor megger failure
Failure when the megger is 1Mohm
or less.
2)
Fan motor disconnection
Standard: The winding resistance
is approximately several ohm.
(It varies depending on the temper-
ature, or while the inner thermo is
operating, it will be
ohm)
- 253 -
Remedy
Connect the short-circuit con-
nector to CN6, and go to sec-
tion [1].
Replace the INV board.
Replace the INV board.
Normal
*Reconnect the short-circuit
connector to CN6 after check-
ing the voltage.
a. Check items [1] through [3]
for problems.
b. Check that high and low
pressures are balanced.
c. Check that no liquid refrig-
erant is present in the
compressor.
→Go to "d." when the
problem persists after
compressor startup was
repeated several times.
If normal operation is re-
stored, check the crank-
case heater for problems.
d. Check that there is a pres-
sure difference between
high and low pressures af-
ter compressor startup.
→Check the high pressure
with LED monitor for
changes.
Replace the compressor if
there is no pressure differ-
ence. (the compressor
may be locked.)
Replace the INV board if there
is a voltage imbalance.
Check the crankcase heater
for problems if there is no volt-
age imbalance.
→When the error occurred, liq-
uid refrigerant may have been
present in the compressor.
Replace the fan motor.