[ IX Troubleshooting ]
2. MA remote controller transmission
The communication between the MA remote controller and the indoor unit is performed with current tone burst.
(1) Symptoms caused by noise interference on the transmission line
If noise is generated on the transmission line, and the communication between the MA remote controller and the indoor unit
is interrupted for 3 minutes in a row, MA transmission error (6831) will occur.
(2) Confirmation of transmission specifications and wave pattern
MA remote controller
Transmission waveform (Across terminal No.1 - 2)
Logic 1
12msec
HWE10140
A
B
Logic 0
Logic 1
Logic 1
12msec
12msec
12msec
TB15
1
A, B : No polarity
2
Across terminal No. 1-2
Indoor unit
: Power supply (9V to 12VDC)
Satisfies the formula
12 msec/bit
DC9~12V
Voltage among terminals must
be between DC9 and 12 V.
- 228 -
5%
GB