Mitsubishi Electric PURY-RP200 Service Handbook page 272

Hide thumbs Also See for PURY-RP200:
Table of Contents

Advertisement

[ IX Troubleshooting ]
Compressor cover
(top)
4. Remove the compressor cover (top).
HWE10140
5. Remove the compressor wires, compressor covers
(right and left), and belt heater.
Protection for the
sealing material
Suction piping
6. Place protective materials on the insulation lining of
the compressor cover and on the sealing material
on the compressor suction pipe to protect them from
the torch flame, debraze the pipe, and replace the
compressor.
- 263 -
Compressor covers
(right and left)
(The inside of the compressor
cover is lined with sound
insulation material.)
Belt heater
Protection for the
compressor cover
GB