Mitsubishi Electric PURY-RP200 Service Handbook page 258

Hide thumbs Also See for PURY-RP200:
Table of Contents

Advertisement

[ IX Troubleshooting ]
4. BC controller transformer
BC controller control board
CNTR
CN03
Red
White
Red
Red
Normal
Abnormal
CNTR(1)-(3)
about 58 ohm.
Open-phase or shorting
CN03(1)-(3)
about 1.6 ohm.
* Before measuring the resistance, pull out the connector.