Mitsubishi Electric PURY-RP200 Service Handbook page 47

Hide thumbs Also See for PURY-RP200:
Table of Contents

Advertisement

[ II Restrictions ]
5. An example of a system in which a system controller is connected to the indoor-outdoor transmission line (except
LM adapter)
(1) Sample control wiring
(2) Cautions
1)
ME remote controller and MA remote controller cannot both be con-
nected to the same group of indoor units.
2)
No more than 2 MA remote controllers can be connected to a group
of indoor units.
3)
Do not connect the terminal blocks (TB5) on the indoor units that are
connected to different outdoor units with each other.
4)
Replacement of male power jumper connector (CN41) must be per-
formed only on one of the outdoor units.
5)
Provide grounding to S terminal on the terminal block for transmis-
sion line for centralized control (TB7) on only one of the outdoor
units.
6)
A maximum of 3 system controllers can be connected to the indoor-
outdoor transmission line, with the exception that only one G(B)-50A
may be connected.
7)
When the total number of indoor units exceeds 20 (12 if one or more
indoor units of the 200 model or above is connected), it may not be
possible to connect a system controller to the indoor-outdoor trans-
mission line.
8)
When the number of the connected indoor units is as shown in the
table below, one or more transmission boosters (sold separately)
are required.
To connect two transmission boosters, connect them in parallel.
(Observe the maximum number of connectable indoor units that are
listed in the specifications for each outdoor unit.)
HWE10140
CN41 CN40 Replace
SW2-1 OFF ON
OC
BC
51
53
TB3
TB02
M1
M2
M1
M2
S
TB7
M1
M2
S
Connect
Leave the male
connector on
CN41 as it is.
SW2-1 OFF ON
OC
BC
55
57
TB3
TB02
M1
M2
M1
M2
S
TB7
M1
M2
S
Not
Note1
Connect
System controller
A B S
L11
Group
Group
IC
IC
01
02
TB5
TB15
TB5
TB15
M1
M2
S
1 2
M1
M2
S
1 2
A
B
A
1
2
1
MA
MA
L21
Group
IC
IC
04
05
TB5
TB5
TB15
TB15
M1
M2
S
1 2
M1
M2
S
1 2
A
B
1
2
MA
m3
Note1 LM adapters cannot be connected to the
indoor-outdoor transmission line.
When the 200 and 250 models are not in-
cluded in the connected indoor units
When the 200 and 250 models are includ-
ed in the connected indoor units
The table above shows the number of transmission boosters that is
required by the system with three BC controllers. For each BC con-
troller that is subtracted from the above-mentioned system, two ad-
ditional indoor units can be connected.
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Maximum distance (1.25mm
L11 200m [656ft]
L21 200m [656ft]
L25 200m [656ft]
2) Transmission line for centralized control
L31+L21 200m [656ft]
3) MA remote controller wiring
Same as [5] 1.
4) Maximum line distance via outdoor unit
2
(1.25mm
[AWG16] or larger)
L25+L31+L11 500m [1640ft]
L11+L31+L21 500m [1640ft]
- 38 -
Interlock operation with
the ventilation unit
Group
LC
IC
03
07
TB5
TB15
TB5
M1
M2
S
1 2
M1
M2
S
B
A
B
2
1
2
MA
Group
LC
IC
08
06
TB5
TB15
TB5
M1
M2
S
1 2
M1
M2
S
A
B
1
2
MA
Number of transmission
booster (sold separately)
required
1 unit
27 - 50
units
21 - 39
units
2
[AWG16] or larger)
2 units
-
40 - 50
units
GB

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pury-rp250Pury-rp300yjm-bmPury-rp300yjm-bPury-rp200

Table of Contents