Controller
Advanced Plus
Fuse
3.0 Amp
Voltage in
24VAC
Voltage output
24VAC
Number of outputs
2
Program 1
2 flush/backpulse cycles
Estimated water use¹
7.5 gal. (28.4 litres)
(US gallons)
Program 2
4 flush/backpulse cycles
Estimated water use
15 gal. (56.7 litres)
(US gallons)
Program 3
2 flush/backpulse cycles,
1 drain cycle
Estimated water use
13.5 gal (51 litres)
(US gallons)
Program 4
2 flush/backpulse cycles,
2 drain cycles
Estimated water use
19.5 gal. (73.7 litres)
(US gallons)
The Advanced Plus controller is capable of running the cleaning cycle 1 per day, twice, four
times, eight times or 24 times per day. The water usage estimate assumes the controller is
running the cleaning cycle once per day.
Controller Specifications
20