Stove Installation

Packing List

Wood Moisture Meter

Floor Protection Requirements

Stove must be placed on the Travis Industries legs or Pedestal.
Floor protection must extend to the sides, rear, and front of the stove (see "Clearances" below for
minimum floor protection).
Floor protection must be non-combustible and at least .018" thick (26 guage).

Stove Placement Requirements

Clearances may be reduced by methods specified in NFPA 211, listed wall shields, pipe shields, or
other means approved by local building or fire officials.
Stove must be placed so that no combustibles are within, or can swing within (e.g. drapes, doors), 36"
of the front of the stove
If the stove is placed in a location where the ceiling height is less than 7', it must follow the
requirements in the section "Alcove Installation Requirements"
Must maintain the clearances to combustibles listed below (drywall, furniture, etc.):

Clearances

The following clearances must be met (see Figure 2 and Figure 3)
Clearance Requirements:
A
Sidewall to stove
B
Backwall to stove
C
Cornerwall to stove
D
Connector to sidewall
E
Connector to backwall
F
Connector to cornerwall
G
Side & Rear Floor Protector
H
Front Floor Protector
*Reduced clearance installations require one of the chimneys and connectors listed below:
AMERI-TEC model DCC with model HS chimney
DURAVENT model DVL with DURATEC or DURA-PLUS chimney
GSW Super Chimney Twenty-One connected directly to appliance
I.C.C. Excel (2100-2 Can.) (103-HT USA) chimney with HP connector
METALFAB model DW connector with TG chimney
OLIVER MACLEOD PROVENT model PV connector with model 3103 chimney
SECURITY model DP connector with SECURITY model ASHT or S2100 chimney
SELKIRK METALBESTOS model DS connector with model SSII chimney
Standard Masonry Chimney with any one of the above listed connectors
NOTE: Reduced clearance connectors may not connect to the flue collar – an appliance adapter may be required.
NOTE: Standard residential installations with reduced clearance connector may use the clearance
determined by the manufacturer of the connector for the connector to wall clearance or the clearance
listed in this manual. Offsets must be used to maintain the stove to wall clearance.
© Travis Industries
(for qualified installers only)
Singlewall Connector
18"
458mm
16.5"
420mm
10"
254mm
27"
686mm
19.5"
496mm
19.5"
496mm
6" 153mm (US)
8" 204mm (Canada)
16" 407mm (US)
18" 458mm (Canada)
100-01332
Reduced Clearance*
13"
331mm
9"
229mm
7.5"
191mm
21.5"
547mm
11.5"
293mm
16.5"
420mm
6" 153mm (US)
8" 204mm (Canada)
16" 407mm (US)
18" 458mm (Canada)