CHIMNEY

Fig.1
THIS PROdUCT IS SUITABLE FOR CHIMNEY
INSTALLATION ONLY.
The stove is a radiant room heater and must be con-
nected to a chimney of the proper size and type. For
ROI the chimney must have a diameter of at least
125mm. It is recommended that a flue liner of diam-
eter 125mm be used to line the chimney, the liner
should be approved for use with solid fuel. See
Fig.1.
For the UK the chimney must have a diameter of at
least 150mm, an adaptor is available where required
to fit between the flue outlet and a 6" flexible flue
liner.
Never connect to a smaller size chimney. Do not
connect to a chimney serving another appliance.
Fig.2
In order for the stove to perform satisfactorily the
A
chimney height must be sufficient to ensure an ade-
quate draught of approximately 12 Pa so as to clear
the products of combustion and prevent smoke
problems into the room.
NOTE: A chimney height of not less than 4.5 metres
measured vertically from the outlet of the stove to
the top of the chimney should be satisfactory.
Alternatively the calculation procedure given in EN
13384-1 may be used as the basis for deciding
whether a particular chimney design will provide suf-
B
ficient draught.
The outlet from the chimney should be above the
roof of the building in accordance with the provisions
of Building Regulations Approved Document J.
It is permitted to connect using a closure plate and a
connection piece from the stove to the closure plate
(See Fig. 4), provided that the chimney is of sound
construction with no leaks or cracks, a clay flue liner
has been used that can withstand up to 1000
clay liner has a diameter no greater than 200mm.
C
If installation is into an existing chimney then it must
be sound and have no cracks or other faults which
might allow fumes into the house. Older properties,
especially, may have chimney faults or the cross
section may be too large i.e. more than 230 mm x
230 mm. Remedial action should be taken, if
required, seeking expert advice, if necessary. If it is
found necessary to line the chimney then a flue liner
suitable for solid fuel must be used in accordance
with Building Regulations Approved Document J.