Parts Specification - Toshiba HFC R407C Service Manual

Super multi split type system
Hide thumbs Also See for HFC R407C:
Table of Contents

Advertisement

Specification of 3-pipe, heat recovery outdoor unit
Model name
Cooling capacity
Heating capacity
Power supply
Cooling
Operating current
Power consumption
EER
Power factor
Heating
Operating current
Power consumption
COP
Power factor
Starting current
Starting method
Sound level
Dimensions (H x W x D)
Net weight
Colour
Compressor
Fan assembly
Refrigeration (charged weight)
Piping connection
Max. equivalent piping length
Max. actual piping length
Max. piping head
Suction accumulator case heater
Notes:
1.
Specifications are subject to change without notice.
2.
The specification shown in ( ) denotes operation with an indoor unit load diversity of 135%.
3.
Operating conditions:
Outdoor temperature °C
Room temperature °C
4.
Sound level: 1 m horizontal from centre.
1.5 m vertical from base.
12

Parts specification

Outdoor unit
kW
kW
A
kW
%
A
kW
%
A
Sound pressure
dB
Sound power
dB(A)
mm
kg
Type
Oil (volume)
ml
Crankcase heater
Motor output
kW
Fan
Motor output
kW
Air flow volume
m
kg
Liquid
mm
Discharge gas
mm
Suction gas
mm
m
m
m
m
W
Cooling
-5 to 43
Heating
-15 to 21
Cooling
18 to 32
Heating
15 to 29
MAR-F105HTM8-PE
25.0 (28.0)
28.0 (31.5)
380-415 V, 3 phase, 50 Hz
17.4 (19.1)
11.8 (12.8)
2.11 (2.19)
98 (97)
17.7 (15.5)
11.8 (10.5)
2.37 (3.0)
96 (98)
60
Direct
58
70
1700 x 990 x 790
285
Silky Shade (Munsell 1-Y8.5/0.5)/RAL 1013 (DE ~9)
Hermetically sealed (twin scroll)
Polyolester NISSEKI RB74AF 74VG (7000)
Internal type
7.5
Propeller fan
0.4
3
/h
10,000
R-407C (19)
15.9 (flare connection)
19.0 (flare connection)
28.6 (brazing connection)
120
100
50: when the outdoor unit is installed above
20: when the outdoor unit is installed below
29 (240 V AC)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents