Valve and sensor function and operation
Outdoor unit - valve functions
Symbol
Name of valve
20SF
4-way reversing valve
(4-way valve)
Cooling operation
4-way reversing valve
Heating operation
SV1
High-pressure release
solenoid valve
SV2
Hot gas bypass solenoid
valve
SV4
Solenoid valve for D.O.L.
compressor start-up
SV5
Gas balance
SV13
Cooling solenoid valve
SV14
Solenoid valve for
expansion valve.
SV15
Sub heat exchanger
solenoid valve
SV16
Solenoid valve for capillary
SV17
Solenoid valve for compressor Open when compressor ON.
PMV1
Cooling bypass flow
control valve
PMV2
Outdoor flow control valve
66
Outdoor unit
Description of function
OFF: Normal operation.
ON: Low load condition when sub heat exchanger is
required. Used in combination with SV15.
ON: Normal operation.
OFF: Defrost operation.
Heating operation.
Energised when TE >11°C
Opens when Pd < 13 kgf/cm
(For cooling-dominant mode and sub heat exchanger
operation Pd < 17 kgf/cm
Opens when outdoor ThO < 0°C
Opens when the D.O.L. compressor starts for
unloading.
Opens when compressor stops.
Opens for cooling-only operations.
SV14 opens for heating operation.
Opens for sub heat exchanger requirement.
SV16 opens for low load conditions during heating-
dominant operation.
Closed when compressor OFF.
Opens when ThD1 or ThD2 > 110°C.
Opens when ThS > 20°C.
Opens during cooling-dominant operation.
Degree of opening depending on cooling/heating
demands.
2
G (ccoling)
2
G - 3-pipe only).