Outline Of Control System - Toshiba HFC R407C Service Manual

Super multi split type system
Hide thumbs Also See for HFC R407C:
Table of Contents

Advertisement

The refrigerant and electrical systems of the Super Multi air conditioner are controlled by the Multi
Controller and the outdoor unit microprocessors.
All RAV heat pump, R-407C, 4/5 series indoor units are compatible with the Super Multi system, i.e. 1~5 HP .
For system operation, initially the microprocessor in each indoor unit calculates the difference between the
current room temperature (TA) and the requested temperature which has been set on the remote
controller. A demand signal is determined and transmitted to the Multi Controller microprocessor in the
form of operation commands (i.e. ON/OFF, cooling or heating operation mode, operation demand frequency).
The Multi Controller microprocessor receives operation commands from all indoor units connected,
calculates the accumulative operation command and transmits this information to the outdoor unit interface
microprocessor.
The interface microprocessor calculates the capacity required for heating or cooling and determines the
operation mode of the outdoor unit and the actual frequency of the compressor.
Control system diagram
Indoor unit 1-A
Fan
Temp. sensor (TA)
Drain pump
Indoor unit microprocessor
Remote controller
1 - B
1 - C
1 - D
2 - A
2 - B
2 - C
2 - D
Introduction

Outline of control system

Multi Controller 1
Capacity rank
setting switch
Temp. sensor
Pulse modulating
valve
Multi Controller microprocessor
Display LED
2-way valve
Multi Controller 2
Multi Controller microprocessor
Outdoor unit
Protection unit
Comp. sensor
Temp. sensor
Pulse modulating
valve
Interface microprocessor
D.O.L. compressor
Display LED
2-way valve
Fan
4-way valve
Communication
PCB
Inverter
compressor
Inverter
IPDU
Protection
Power
unit
supply
9