Dacor Discovery EO127 Installation Instructions Manual page 13

Hide thumbs Also See for Discovery EO127:
Table of Contents

Advertisement

Connecting to a Three Wire Electrical
System - Where Local Codes Permit
WARNING
Do not connect the green appliance conduit wire to the
neutral (white) junction box wire unless local building
codes permit.
1.
Separate the wires coming out of the appliance conduit.
2.
Connect the green and white wires from the appliance
conduit to the white (neutral) supply wire in the junction
box.
3.
Connect the black wire from the appliance conduit to
the black (L1) supply wire in the junction box.
4.
Connect the red wire from the appliance conduit to the
red (L2) supply wire in the junction box.
Junction box
RED
RED
3 Wire Junction Box Connection -
(Where Local Codes Permit)
Installation Instructions
Cable from circuit breaker
panel or fuse box
GREEN
WHITE
WHITE
BLACK
BLACK
Wire nut
(3 places)
Conduit to
wall oven
Connecting to a Three Wire Electrical
System with External Ground - Where Local
Codes Permit
WARNING
Do not connect the green appliance wire to the junc-
tion box or to a cold water pipe unless local building
codes permit.
Do not ground the appliance to a gas supply pipe or
hot water pipe.
If connecting the ground wire to a grounded cold
water pipe, connect using a separate copper
grounding wire (No. 10 minimum) and a clamp with
an external grounding screw. The grounded cold
water pipe must have metal continuity to electrical
ground and must not be interrupted by insulating
materials. Any insulating materials must be jumped,
with a minimum, 4 AWG wire to establish continuity
to ground.
No. 4
copper wire
Metal water
pipe
Jumpering an Insulated Pipe
If the junction box has been properly grounded by a
licensed electrician, the green (ground) wire from the
appliance conduit may be connected to the junction box
using a loop terminal.
See the diagram on the following page. To connect the
green appliance conduit wire to a grounded cold water
pipe:
1.
Separate the wires coming out of the appliance conduit.
2.
Connect the white wire from the appliance conduit to
the white (neutral) supply wire in the junction box.
3.
Connect the black wire from the appliance conduit to
the black (L1) supply wire in the junction box.
4.
Connect the red wire from the appliance conduit to the
red (L2) supply wire in the junction box.
5.
Connect the green wire from the appliance conduit to a
grounded cold water pipe as shown. Jumper any insu-
lating materials as shown above with a length of No. 4
copper wire. Securely clamp the wire to bare metal at
both ends.
Meter
Clamps
Bare metal
NOtE