Pipe Length And The Elevation - Toyotomi TPN A128 IVP Service Manual

Table of Contents

Advertisement

6.3 Pipe length and the elevation

The pipe length and refrigerant amount:
Model
TPN A128 IVP
TPG A128 IVP
+
TPN A135 IVP
TPG A135 IVP
+
TPN A180 IVP
TPG A180 IVP
+
TPN A240 IVP
TPG A240 IVP
+
Caution:
The capacity test is based on the standard length and the maximum permissive length is based on the
system reliability.
The oil trap should be installed per 5-7 meters.
Pipe size
Standard
length
Gas
Liquid
3/8''
1/4''
(Ф9.52)
(Ф6.35)
1/2''
1/4''
(Ф12.7)
(Ф6.35)
5/8''
3/8''
(Ф15.9)
(Ф9.52)
15
Max.
Elevation
Length
(m)
B (m)
A (m)
5
8
5
8
5
10
5
10
Max.
Additional
refrigerant
(g/m)
20
20
20
20
25
20
25
40

Hide quick links: