Rear Vent Configurations with Horizontal Termination and No Rise

Use 8" Diameter Vent with a 6-5/8" to 8" adapter (increaser). We recommend using the minimum
vent kit from Travis Industries (SKU 96200311). This kit contains the following components used to
vent the stove through a typical exterior wall:
-- 6-5/8" to 8" Adapter (Black)
-- Thimble (2 pieces)
Place the 6-5/8" to 8" adapter directly onto stove (see illustration below).
Maximum Horizontal Run of 4'.
On LP configurations with an extended vent configuration (more than 3.9" horizontal section) a 14"
snorkel is required. A high-wind horizontal cap is required for all other installations(see below).
NG Applications
LP Applications
Min. Vent Configuration
(one 3.9" horizontal section)
Typical 8-1/2" (216mm)
6-5/8" to 8" Adapter
Horizontal sections require a ¼" (6mm) rise every 12"
(305mm) of travel.
Maximum of one (1) 45° elbow may be used between
horizontal sections.
Diffuser must be set to closed (#2) position.
Intake restrictor set to #1 (stock).
Exhaust restrictor must be set to the #1 (stock) position
except for LP extended vent configurations (remove the
exhaust restrictor and replace the screws).
Do not install the intake damper plate or exhaust
restrictor extender plates.
© Travis Industries
Installation
Typical 8-1/2" (216mm)
6-5/8" to 8" Adapter
One 3.9" Horiontal Section Only
High Wind Horizontal Cap
Required (58DVA-HC)
Min. 12" (305mm)
Grade
Thimble w Cover
(for qualified installers only)
-- Pipe Section (3.9")
-- High-Wind Horizontal Cap
Max. 4' (1.2M) - one 45 deg. elbow allowed.
High Wind Horizontal Cap
Required (58DVA-HC)
Min. 12" (305mm)
Grade
Thimble w Cover
Extended Vent Configuration
(Max. 4' Run - one 45 deg. elbow allowed)
- Remove Exhaust Restrictor (replace screws)
Max. 4' (1.2M) - one 45 deg. elbow allowed.
6-5/8" to 8" Adapter
Typical Flue Center
4121120
--- Thimble Cover (Black)
14" Snorkel Cap Required
(58DVA-SNK14)
Min. 12" (305mm)
Grade
Thimble w Cover
Corner Installations
5-3/8" (137mm)
Minimum 9"
(229mm)
100-01315
Minimum 52"
(1321mm)