Gas Line Installation

!
The gas line must be installed in accordance with all local codes, if any; if not, follow current ANSI
Z223.1 or NFPA 54 in the USA and the current CGA B149 in Canada.
!
The heater and gas control valve must be disconnected from the gas supply piping during any
pressure testing of that system at test pressures in excess of 1/2 psig (3.45 kPA). For pressures
under 1/2 psig (3.45 kPA), isolate the gas supply piping by closing the manual shutoff valve.
This heater is designed for natural gas but can be converted to propane. Check the stic ker on top of
the gas control valve to verify the correct fuel is used (see page 4).
Leak test all gas line joints and the gas control valve prior to and after starting the heater.
The location of the gas inlet is shown below
A manual shutoff valve is required for installation (it must be located within 3' of the heater).
T-Handle gas cocks are required in Massachusetts in compliance with code 248CMR.
This stove is shipped with a 16" long, 3/8" diameter flex gas line attached to an elbow on the gas
control valve (see illustration below for location). The flex accepts a 3/8" flare fitting.

Gas Inlet Pressure

With the heater off, the inlet pressure must meet the requirements listed in the table below
If the pressure is not sufficient, make sure the piping used is large enough and the total gas load for
the residence does not exceed the amount supplied.
The supply regulator (the regulator that attaches directly to the residence inlet or to the propane tank)
should supply gas at the suggested input pressure listed below. Contact the local gas supplier if the
regulator is at an improper pressure.
© Travis Industries
Installation
Standard Input Pressure
Natural Gas
Propane
(for qualified installers only)
7" W.C. (1.74 Kpa)
13" W.C. (3.23 Kpa)
4121120
100-01315