Fireplace Installation; Check Gas Type - Monessen Hearth MDV500, MDV600 Installation & Operating Instructions Manual

Mdv series direct vent gas fireplace
Hide thumbs Also See for MDV500, MDV600:
Table of Contents

Advertisement

MDV Series Direct Vent Gas Fireplace
checK gas type
Use proper gas type for the fireplace you are installing.
If you have conflicting gas type, do not install fireplace.
See dealer where you purchased the fireplace for proper
fireplace according to your gas type.
gas pIpe InstallatIon
a qualified installer or service person must 
connect  appliance  to  gas  supply.  follow 
all local codes.
InstallatIon Items needed
Before installing fireplace and burner system, make sure
you have the items listed below.
Tee joint
Equipment shutoff valve*
Sediment trap (recommended)
External regulator (supplied by installer)
Piping (check local codes)
Sealant (resistant to propane/LP gas)
approved flexible gas line with gas connector (if
allowed by local codes — not provided)
* A CSA design-certified equipment shutoff valve with
1/8" NPT tap is an acceptable alternative to test gauge
connection. Purchase the CSA design-certified equip-
ment shutoff valve from your dealer.
For propane/LP connections only, the installer must supply
an external regulator. The external regulator will reduce
incoming gas pressure. You must reduce incoming gas
pressure to between 11 and 13 inches of water. If you do
not reduce incoming gas pressure, burner system regula-
tor damage could occur. Install external regulator with the
vent pointing down as shown in Figure 45. Pointing the
vent down protects it from freezing rain or sleet.
for  propane/lp  units,  never  connect 
fireplace directly to the propane/lp supply. 
this  burner  system  requires  an  external 
regulator (not supplied). Install the external 
regulator between the burner system and 
propane/lp supply.
28
Pipe wrench
Test gauge connection*
fIreplace InstallatIon 
External
Regulator
Figure 45 -
External Regulator with Vent Pointing Down
(Propane/LP Only)
FP1977
external regulator
use  only  new  black  iron  or  steel  pipe. 
Internally  tinned  copper  or  copper  tubing 
can be used per national fuel code, section 
2.6.3, providing gas meets hydrogen sulfide 
limits, and where permitted by local codes. 
gas piping system must be sized to provide 
minimum inlet pressure (listed on data plate) 
at the maximum flow rate (Btu/hr). undue 
pressure  loss  will  occur  if  the  pipe  is  too 
small.
external regulators may be necessary for 
natural  gas.  one-  or  two-pound  systems 
will damage this appliance and may cause 
fire hazard.
When using copper or flex connectors use only fittings
approved for gas connections. The gas control inlet is
3/8" NPT.
100 gal. (min)
Propane/LP
Supply Tank
Vent Pointing
Down
FP1977
75D2523