Check Gas Pressure - Millivolt; Electrical Wiring - Monessen Hearth MDV500, MDV600 Installation & Operating Instructions Manual

Mdv series direct vent gas fireplace
Hide thumbs Also See for MDV500, MDV600:
Table of Contents

Advertisement

MDV Series Direct Vent Gas Fireplace
1. Check gas type. The gas supply must be the same as
stated on the appliance's rating decal. If the gas supply
is different from the fireplace, stop! Do not install the
appliance. Contact your dealer immediately.
2. To ease installation, a 18" (457 mm) flex line with manual
shut-off valve has been provided with on this appliance.
Install and attach 1/2" gas line onto shut-off valve.
3. After completing gas line connection, purge air from
gas line and test all gas joints from the gas meter
to the fireplace for leaks. Use a solution of 50/40
water and soap or a gas sniffer.
4. To adjust flame height, turn HI/LO knob to HI to get
maximum pressure to burner. Turn HI/LO knob to
LO to get minimum pressure.
5. To check gas pressures at valve, turn captured
screw counter clockwise 2 or 3 turns and then place
tubing to pressure gauge over test point. Turn unit
to high. Figure 47. After taking pressure reading,
be sure and turn captured screw clockwise firmly
to reseal. Do not over torque. Check test points for
gas leaks.
note:  captured  screws  for  pressure  reading  are 
located in the same place in both valve types — millivolt 
and electronic.
electrIcal wIrIng
This fireplace will work without any electrical supply except
to operate blower and electronic ignition system.
note: If installed in mobile home, fireplace must be bolted
securely to floor.
electrical   co nne c t ions   s hould   on l y 
be  performed  by  a  qualified,  licensed 
electrician.  main  power  must  be  off  when 
connecting to main electrical power supply 
or  performing  service.  all  wiring  shall  be 
in compliance with all local, city and state 
codes. the appliance, when installed, must 
be electrically grounded in accordance with 
local codes or in the absence of local codes, 
with the national electrical code ansI/nfpa 
70  (latest  edition)  and  canadian  electrical 
code, csa c22.1.
30
checK gas pressure and electrIcal InstallatIon - mIllIVolt
Pressure
Test "IN"
Pressure
Test "OUT"
HI/LO Knob
Pilot Adjustment Screw
Figure 47 -
Gas Pressure Check at Gas Valve
FP1979
do  not  use  open  flame  to  check  for  gas 
Millivolt gas valve
leaks.
label all wires before disconnecting when 
servicing controls. wiring errors can cause 
improper and dangerous operation.
Verify proper operation after servicing.
FP1979
75D2523