Stove Placement Requirements; Floor Protection Requirements; Gas Line Installation - Lopi Heritage Bay DV Owner's Manual

Freestanding direct-vent stove natural gas or propane residential or mobile home
Table of Contents

Advertisement

S
Heater Placement Requirements
¥
Heater must be installed on a level surface capable of supporting the heater and vent
¥
Due to the high temperature of the heater, it should be located out of traffic and away from furniture
and draperies. Heater must be placed so no combustibles are within, or can swing within 36" (910
mm) of the front of the heater (e.g. drapes, doors)
? When placed in a location where the floor to ceiling height is under 7 feet (2130 mm), the
installation is considered an alcove and must meet the following requirements:
¥
The alcove floor to ceiling height must be at least 60" (1520 mm) tall
¥
The alcove must not be more than 48" (1220 mm) deep before the ceiling returns to 7' (2130 mm)
¥
The alcove must be at least 43-3/8" (1100 mm) wide
¥
The heater must not be placed so the vents below or above the door, along the sides of heater, or
along the back of the heater can become blocked.
Floor Protection
¥
When the stove is installed directly on carpeting, vinyl or other combustible material other than
wood flooring, the stove must be installed on a metal or wood protection panel extending the full
width and depth of the heater (Minimum 27-3/8" (695 mm) wide by 20-3/8" (518 mm) deep ).

Gas Line Installation

!
The gas line must be installed in accordance with all local codes, if any; if not, follow ANSI Z223.1
and the requirements listed below.
!
The heater and gas control valve must be
disconnected from the gas supply piping during
any pressure testing of that system at test
pressures in excess of 1/2 psig (3.45 kPA). For
pressures under 1/2 psig (3.45 kPA), isolate the
gas supply piping by closing the manual
shutoff valve.
¥
This heater is designed for natural gas but can
be converted to propane. Check the sticker on
the top of the gas control valve to make sure
the correct fuel is used.
¥
Leak test all gas line joints and the gas control
valve prior to and after starting the heater.
¥
The gas inlet accepts a 3/8" F.P.T. Fitting
¥
The location of the gas inlet is shown below
¥
A manual shutoff valve is required for
installation (it must be located within 3' (910
mm) of the heater)
Gas Inlet Pressure
¥
With the heater off, the inlet pressure must meet the requirements listed in the table below
? If the pressure is not sufficient, make sure the piping used is large enough and the total gas load for
the residence does not exceed the amount supplied.
? The supply regulator (the regulator that attaches directly to the residence inlet or to the propane tank)
should supply gas at the suggested input pressure listed below. Contact the local gas supplier if the
regulator is at an improper pressure.
I
TOVE
NSTALLATION
Standard Input Pressure
Natural Gas
Propane
(C
.)
ONT
7" W.C. (1.74 Kpa)
11" W.C. (2.73 Kpa)
- For Qualified Installers Only!
Center
of
Heater
6-1/4Ó
(156 mm)
P
7
AGE
From
Front of
Heater
17-1/2"
(445 mm)
3Ó (76
mm)