NOTE: If the variable- -speed indoor equipment (furnace or fan
coil) cannot be found, the User Interface will display "CANNOT
COMMUNICATE WITH INDOOR UNIT". This MUST be
corrected before the initial power up sequence can continue. If
indoor unit is found, but outdoor unit is not found, "OUTDOOR
UNIT NOT IDENTIFIED" will appear. Proceed to the next section
for Outdoor Unit Identification.
Selecting Outdoor Unit
If there is no communicating outdoor unit, the screen, shown in
Fig. 17, will appear. Press either Time or Temp +/- - buttons to
select AC (air conditioner), HP (heat pump), or None (no unit
installed). Press right- -side button to continue to next screen.
OUTDOOR UNIT
OUTDOOR UNIT
NOT IDENTIFIED
ENTER HEAT PUMP
SELECT TYPE:
NONE
SIZE
NONE, AC, HP
18000 TO 60000 BTU
PRESS +/- TO MAKE
PRESS +/- TO MAKE
SELECTION
SELECTION
CONTINUE
BACK
Fig. 17 - - Selecting Outdoor Unit
If either AC or HP has been selected as the outdoor unit type, the
middle screen will appear (See Fig. 17). Press either Time or Temp
+/- - buttons to select appropriate Btu size of outdoor unit, then
press right side button to continue. If a NIM (Network Interface
Module) is applied for non- -communicating two- -stage outdoor
equipment, select 1 or 2- -stage compressor operation, and press
right- -side button to continue.
NOTE: Range of outdoor unit Btu selection is limited by model
number of indoor unit installed. The Infinity Zone Control will not
allow an outdoor unit size that is not supported by the installed
indoor unit.
NOTE: On new system installations, the model and serial number
will be recognized and displayed. On any indoor/outdoor board
replacements, the equipment will be recognized but the exact
model/serial number will not be displayed.
Selecting Electric Heater
If the equipment is a fan coil, packaged heat pump, or packaged
AC and the electric heater is not self- -identifying, "ELECTRIC
HEATER NOT IDENTIFIED" will appear (See Fig. 18). Press
either Time or Temp +/- - buttons to select appropriate size of
electric heater installed, then press right- -side button to continue.
An asterisks (*) will appear next to electric heater sizes that may
cause excessive airflow.
ELECTRIC HEATER
NOT IDENTIFIED
ENTER SIZE:
NONE, 5,10,15 KW
PRESS +/- TO MAKE
SELECTION
BACK
Fig. 18 - - Selecting Electric Heater
NOTE: Range of electric heaters available is limited by model
number of the equipment installed. The Infinity Zone Control will
not allow an electric heater size that is not supported by the
installed equipment.
OUTDOOR UNIT
HEAT PUMP
36000 BTU
ENTER NUMBER OF
SPEEDS, 1 or 2:
1
PRESS +/- TO MAKE
SELECTION
CONTINUE
BACK
CONTINUE
A03196
5 KW
CONTINUE
A03197
Hydronic Heat Applications
The - -B model of the Infinity Zone Control supports Hydronic
Heat applications in the form of a hot water coil on FE fan coils
only. If an FE fan coil is installed, a Hydronic Heat kit should be
installed in place of the electric heater. See FE fan coil Product
Data for accessory part number. The system will identify that
hydonic heat has been installed during the initial commissioning
process. The system will treat the hot water coil as either auxiliary
heat in a heat pump application, or the sole heat source. Setup
options for Hydronic Heat applications are described in the Setup
section of this instruction.
Selecting Accessories
Once the indoor and outdoor equipment have been found or
entered, the following screens will appear allowing the Installer to
select the "AIR FILTER TYPE; HUMIDIFIER INSTALLED";
and "UV LIGHTS INSTALLED" (See Fig. 19). Use either Time or
Temp +/- - buttons to make appropriate selections in the highlighted
area on the display screen. Press right- -side button to continue (or
advance) to the next screen.
ACCESSORIES
ACCESSORIES
AIR FILTER TYPE:
HUMIDIFIER
EAC
EAC
INSTALLED?
MEDIA
MEDIA + EAC
PRESS +/- TO MAKE
PRESS +/- TO MAKE
SELECTION
SELECTION
CONTINUE
BACK
AIR FILTER MEDIA TYPE
HUMIDIFIER INSTALLED?
Fig. 19 - - Accessories —UV Lights
Air Filter Type
This accessory screen will appear first. The installer will need to
enter the type of filter (MEDIA, EAC, or both). See Table 1 and
make a selection using Time or Temp +/- - button, then press
right- -side button to continue.
Table 1 – Filter Selection
INSTALLED FILTER
1 inch to 4 inch media
High voltage EAC
High voltage EAC + 1 to 4 inch media
Infinityt Air Purifier
Humidifier Installed
This will appear after the Air Filter Type screen. Select whether a
humidifier is installed on the system, YES or NO, then press
right- -side button to continue.
UV Lights Installed
This screen will appear to select whether UV lights are installed on
the system, select YES or NO, then press right- -side button to
continue.
Zoning
"SEARCHING FOR ZONE EQUIPMENT" will appear on the
screen to identify the number of zones detected. This screen will
show Zone 1, Zone 2, etc. and indicate all zones having either a
Remote Room Sensor, or smart sensors associated with them. If the
system contains smart sensors, they must be assigned a zone
number before continuing. See Smart Sensor Installation
Instructions on how to assign Smart Sensors to their respective
7
ACCESSORIES
U.V. LIGHTS
YES
INSTALLED?
YES
PRESS +/- TO MAKE
SELECTION
CONTINUE
BACK
CONTINUE
U.V. LIGHTS INSTALLED?
A03198
MENU
SELECTION
MEDIA
EAC
MEDIA + EAC
MEDIA