Carrier 50TCQD Installation Instructions Manual page 23

Single package rooftop with puron (r-410a) refrigerant sizes 17 & 24
Hide thumbs Also See for 50TCQD:
Table of Contents

Advertisement

Connect T- - 56 - - See Fig. 32 for T- - 56 internal
connections. Install a jumper between SEN and SET
terminals as illustrated. Connect T- - 56 terminals to TB1
terminals 1, 3 and 5 (see Fig. 33).
1
2
3
4
5
6
WHT(GND)
SEN
SET
SW1
BRN (GND)
BLU (SPT)
Cool
Warm
Fig. 32 - - T- - 56 Internal Connections
SEN
SEN
Jumper
SET
SET
Fig. 33 - - PremierLink T- - 56 Sensor
Connect Thermostat — A 7- - wire thermostat connection
requires a 24- - v power source and a common connection.
Use the R and C terminals on the CTB's THERMOSTAT
connection strip for these. Connect the thermostat's Y1,
Y2, W1, W2 and G terminals to PremierLink TB1 as
shown in Fig. 34.
RED(+)
CCN COM
BLK(-)
BLK
(T56)
SENSOR WIRING
JUMPER
TERMINALS
AS SHOWN
C08202
TB1
PL
1
J6-7
PL
TB1
J6-6
3
J6-5
5
C08213
If the 50TCQD unit is equipped with factory- - installed
smoke detector(s), disconnect the factory BLU lead at
TB1- - 6 (Y2) before connecting the thermostat. Identify the
BLU lead originating at CTB- - DDC- - 1; disconnect at
TB1- - 6 and tape off. Confirm that the second BLU lead at
TB1- - 6 remains connected to PremierLink J4- - 8.
SPACE
THERMOSTAT
THERMOSTAT
R
G
Y1
Y2
W1
W2
C
Fig. 34 - - Space Thermostat Connections
If the 50TCQD unit has an economizer system and
free- - cooling operation is required, a sensor representing
Return Air Temperature must also be connected
(field- - supplied and installed). This sensor may be a T- - 55
Space Sensor (see Fig. 31) installed in the space or in the
return duct, or it may be sensor PNO 33ZCSENSAT,
installed in the return duct. Connect this sensor to TB1- - 1
and TB1- - 3 per Fig. 31.
Configure the unit for Thermostat Mode — Connect to the
CCN bus using a CCN service tool and navigate to
PremierLink Configuration screen for Operating Mode.
Default setting is Sensor Mode (value 1). Change the
value to 0 to reconfigure the controller for Thermostat
Mode.
When the PremierLink is configured for Thermostat
Mode, these functions are not available: Fire Shutdown
(FSD), Remote Occupied (RMTOCC), Compressor Safety
(CMPSAFE), Supply Fan Status (SFS), and Filter Pressure
Switch (FILTER).
23
CTB
R
TB1
PL
2
J4-12
J4-10
4
J4-8
6
8
J4-6
J4-4
10
CTB
C
THERMOSTAT
C08119