Download Print this page

Specifications - INFOSEC 5000 User Manual

5000(s) / 6000(s) / 10k(s)
Hide thumbs Also See for 5000:

Advertisement

Available languages

Available languages

6. Specifications

INPUT
Battery mode transfer
Low voltage
range
Low Line comeback
Battery mode transfer
High voltage
range
High Line comeback
Frequency range
Phase
Power factor
OUTPUT
Voltage
AC voltage regulation
Frequency range (synchronized range)
Frequency range (battery mode)
Current crest ratio
Harmonic distortion
AC mode to battery mode
Transfer time
Inverter to Bypass
Waveform
Backup time
Output outlets IEC 10A (or NEMA 110V)
standards/programmables
Output terminal standard/programmable
EFFICIENCY
AC mode
Battery mode
INFOSEC UPS SYSTEM – 4 rue de la Rigotière – 44700 Orvault – France – www.infosec-ups.com
65
Hot Line Tel : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – hotline@infosec.fr – 07 11 AA 59 203 09
E4 LCD
5000 (S)
5000 VA
4000 W
110 V
230 V
176 VAC at 100% load / 110 VAC at 50% load
110 V
230 V
186 VAC at 100% load / 120 VAC at 50% load
110 V
230 V
110 V
230 V
46~54 Hz at 50Hz / 56~64 Hz at 60Hz
46 ~ 54 Hz at 50 Hz / 56 ~ 64 Hz at 60 Hz
50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
From 8 to 30 minutes depending on connected load
2 / 0
yes / yes
E4 LCD
6000 (S)
6000 VA
4800 W
-
-
-
300 VAC
-
290 VAC
Single phase with ground
≧ 0.99 at 100% load
208-220-230-240 VAC
± 1%
3:1 max
≦ 2% THD (Linear load)
≦ 6% THD (Non linear load)
Zero
Zero
Pure Sinewave
2 / 0
yes / yes
89%
88%
E4 LCD
10k (S)
10000 VA
8000 W
2 / 0
yes / yes

Hide quick links: