Download Print this page

Ups Installation For A Parallel System - INFOSEC 5000 User Manual

5000(s) / 6000(s) / 10k(s)
Hide thumbs Also See for 5000:

Advertisement

Available languages

Available languages

2-4. UPS Installation for a Parallel System

If the UPS is only available for a single operation, you can skip this section.
1) Install and wire the UPS according to the section 2-3.
2) Connect the output wires from each UPS to an output breaker.
3) Connect all output breakers to a major output breaker. This major output breaker will then be directly
connected to the loads.
4) Each UPS is connected to an independent battery pack.
NOTE: The parallel system cannot use one battery pack. This would cause permanent system failure.
5) Refer to the following wiring diagram:
Wiring diagram of parallel system
INFOSEC UPS SYSTEM – 4 rue de la Rigotière – 44700 Orvault – France – www.infosec-ups.com
45