2-3. Single UPS Installation

Installation and wiring must be performed in accordance with the local electric laws/regulations and execute the
following instructions by professional personnel.
6)
Make sure the mains wire and breakers in the building are enough for the rated capacity of UPS to avoid the
hazards of electric shock or fire.
NOTE: Do not use the wall receptacle as the input power source for the UPS, as its rated current is less than the
UPS's maximum input current. Otherwise the receptacle may be burned and destroyed.
7) Switch off the mains switch in the building before installation.
8) Turn off all the connected devices before connecting to the UPS.
9) Prepare wires based on the following table:
Model
Input
10K
8
10K S
8
15K
6
15K S
6
20K
6
20K S
6
NOTE 1: The cable for 10K TM / 10K STM should be able to withstand over 63A current. It is recommended to use
8AWG / 16mm² or thicker wire for safety and efficiency.
NOTE 2: The cable for 15K TM / 15K STM should be able to withstand over 75A current. It is recommended to use
6AWG / 16mm² or thicker wire for safety and efficiency.
NOTE 3: The cable for 20K TM / 20K STM should be able to withstand over 100A current. It is recommended to use
6AWG / 25mm² or thicker wire for safety and efficiency.
NOTE 4: The selections for color of wires should be followed by the local electrical laws and regulations.
INFOSEC UPS SYSTEM – 4 rue de la Rigotière – 44700 Orvault – France – www.infosec-ups.com
Hot Line Tel : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – hotline@infosec.fr – 03 15 37 59 204 03
Wiring spec (AWG)
Output
Battery
8
8
8
6
6
6
6
6
6
Ground
8
8
6
6
6
6