Carrier 42C Series Product Data page 23

Fan coil 50/60 hz 150 to 2000 cfm
Table of Contents

Advertisement

ENTHALPY AT SATURATION
ENTHALPY AT
TEMPERATURE
SATURATION
(F)
(Btu per lb.
of dry air)
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
ALTITUDE COOLING CORRECTION FACTORS
ELEVATION (ft)
TOTAL HEAT
1000
.990
2000
.980
3000
.970
4000
.960
5000
.940
6000
.930
7000
.920
8000
.910
9000
.900
AIRFLOW CORRECTION FACTORS
CFM RATIO
TOTAL (Ct)
(Actual/Base)
1.40
1.35
1.30
1.25
1.20
1.15
1.10
1.05
1.00
0.95
0.90
0.85
0.80
0.75
0.70
0.65
0.60
0.55
0.50
0.45
0.40
0.35
0.30
0.25
LEGEND
CFM — Cubic Feet per Minute
Cs
— Sensible Airflow Correction Factor
Ct
— Total Airflow Correction Factor
ESP — External Static Pressure
TEMPERATURE
(F)
15.230
60
15.697
61
16.172
62
16.657
63
17.149
64
17.650
65
18.161
66
18.680
67
19.211
68
19.751
69
20.301
70
20.862
71
21.436
72
22.020
73
22.615
74
23.22
75
23.84
76
24.48
77
25.12
78
25.78
79
80
SENSIBLE HEAT
.960
.930
.896
.864
.830
.800
.770
.750
.730
SENSIBLE (Cs)
1.25
1.26
1.22
1.23
1.19
1.20
1.16
1.17
1.13
1.14
1.10
1.11
1.07
1.08
1.04
1.04
1.00
1.00
0.97
0.97
0.94
0.93
0.90
0.89
0.86
0.85
0.82
0.81
0.78
0.77
0.74
0.72
0.70
0.67
0.66
0.62
0.62
0.57
0.58
0.52
0.53
0.47
0.48
0.42
0.43
0.38
0.38
0.33
ENTHALPY AT
SATURATION
(Btu per lb
of dry air)
26.46
27.15
27.85
28.57
29.31
30.06
30.83
31.62
32.42
33.25
34.09
34.95
35.83
36.74
37.66
38.61
39.57
40.57
41.58
42.62
43.69
STEAM PRESSURE CORRECTION FACTORS
ENTERING AIR
TEMP (F)
40
50
60
70
NOTE: Steam Heating Capacity (Btuh) = Base Capacity x Pressure
Correction Factor x SH (SH value found in Cooling Capacity Correction
Factors table on page 60).
STEAM PRESSURE (PSIG)
2
5
1.202
1.265
1.134
1.196
1.067
1.125
1.000
1.054
23