Carrier 42C Series Product Data page 17

Fan coil 50/60 hz 150 to 2000 cfm
Table of Contents

Advertisement

SYMBOL/SKETCH
FLOW
LEGEND
Cv — Coefficient of Velocity
DX — Direct Expansion
PIPING COMPONENTS (cont)
DESCRIPTION
PRESSURE TEST PORT: Brass body
vice access fitting with removable depressor
type core.
Application — Installed on both sides of the
coil to allow for pressure sensing. Attach
pressure gages to facilitate close tolerance
water balancing.
GAGE COCK: Brass shut-off valve with
1
/
FPT fitting for attachment of pressure
4
gages.
Application — Installed on both sides of the
coil to allow for pressure sensing. Attach
pressure gages to facilitate close tolerance
water balancing. May be used in bleed
bypass line to regulate water flow.
CIRCUIT SETTER: Variable water flow bal-
ancing valve with manual adjustment knob,
pointer, percent-open scale, memory stop
and integral pressure read-out ports.
Application — Used for close tolerance water
flow balancing. Positive shut-off ball valve
feature allows usage as combination balanc-
ing and shut-off valve.
BALANCE VALVE: Variable water flow man-
ual balancing valve with screwdriver slot
adjustment screw.
Application — Often used in conjunction with
test port fittings for water flow balancing. Bal-
ance by temperature differential or coil pres-
sure drop (check specifications for service
fittings required if balancing by pressure
drop). May be used in 3-way valve bypass
line to permit equal flow balancing.
FIXED FLOW VALVE: Flexible orifice type
(non-adjustable).
Application — Used for water flow balancing.
Valve automatically adjusts the flow to within
10% of set point. Requires 15 psi
(35 ft) of additional pump head for proper
operation.
C
FACTOR
V
1
/
3
/
2
4
1
/
ser-
4
N/A
N/A
N/A
N/A
2.12
3.9
3.0
8.9
Valve orifice size
determines C
fac-
V
tor. The orifice of
these fixed flow
valves changes as
flow is regulated.
As the water pres-
sure increases,
the orifice size
decreases,
thereby automati-
cally limiting the
flow rate to the
specified gpm
(±10%).
RATING
STEAM
USE
PSI
F
400
210
NO
200
250
N/A
300
250
NO
150
200
NO
150
160
NO
17