To access this display from the LID default screen:
1. Press
MENU
.
2. Press SERVICE .
3. Scroll down to highlight EQUIPMENT SERVICE.
4. Press SELECT .
5. Scroll down to highlight SERVICE1.
6. Press SELECT .
DESCRIPTION
Motor Temp Override*
Cond Press Override
Refrig Override Delta T
Chilled Medium
Brine Refrig Trippoint
Compr Discharge Alert
Bearing Temp Alert
Water Flow Verify Time
Oil Press Verify Time
Water/Brine Deadband
Recycle Restart Delta T
Recycle Shutdown Delta†
Surge Limit/HGBP Option
Select: Surge=0, HGBP=1
Surge/HGBP Delta T1
Surge/HGBP Delta P1
Min. Load Points (T1/P1)
Surge/HGBP Delta T2
Surge/HGBP Delta P2
Full Load Points (T2/P2)
Surge/HGBP Deadband
Surge Delta Percent Amps
Surge Time Period
Demand Limit Source
Select: Amps=0, Load=1
Amps Correction Factor
Motor Rated Load Amps
Motor Rated Line Voltage
Meter Rated Line KW
Line Frequency
Select: 0=60 Hz, 1=50 Hz
Compr Starter Type
Condenser Freeze Point
Soft Stop Amps Threshold
Stop to Start Timer†
NOTE:
= delta degrees.
*Information is applicable to hermetic machines only.
†Information is applicable to open-drive machines only.
Table 2 — LID Screens (cont)
EXAMPLE 7 — SERVICE1 DISPLAY SCREEN
CONFIGURABLE RANGE
150-200 (66-93)
90-200 (620-1379)
2-5 (1-3)
Water/Brine
8-40 (–13.3-4)
125-200 (52-93)
165-210 (74-99)
0.5-5
15-300
0.5-2.0 (0.3-1.1)
2.0-10.0 (1.1-5.6)
0.5-4.0 (.27-2.2)
0/1
0.5-15 (0.3-8.3)
30-170 (207-1172)
0.5-15 (0.3-8.3)
30-170 (207-1172)
1-3 (0.6-1.6)
10-50
1-5
0/1
1-8
1-9999
1-9999
1-9999
0/1
REDUCE/FULL
–20-35 (–28.9-1.7)
40-100
3-50
UNITS
REFERENCE POINT NAME
DEG F (DEG C)
mt
PSI (kPa)
cp
DEG F (DEG C)
ref
medium
DEG F (DEG C)
br
DEG F (DEG C)
cd
DEG F (DEG C)
tb
MIN
wflow
SEC
oilpr
DEG F (DEG C)
cw
DEG F (DEG C)
rcycrdt
rcycsdt
srg
DEG F (DEG C)
hgb
PSI (kPa)
hgb
DEG F (DEG C)
hgb
PSI (kPa)
hgb
DEG F (DEG C)
hgb
%
surge
MIN
surge
dem
corfact
AMPS
a
VOLTS
v
kW
kw
HZ
freq
starter
DEG F (DEG C)
cdfreeze
%
softstop
MIN
stopmtr
31
DEFAULT VALUE
over
200 (93)
over
125 (862)
over
3 (1.6 )
WATER
trip
33 (1)
alert
200 (93)
alert
210 (99)
t
5
t
15
db
1.0 (0.6)
5 (2.8)
1.0 (0.6)
hgbp
0
dt1
1.5 (0.8)
dp1
50 (345)
dt2
10 (5.6)
dp2
85 (586)
dp
1 (0.6)
a
25
t
2
src
0
3
fs
200
fs
460
fs
600
0
REDUCE
34 (1)
100
20
1197