Tekmar 403 Installation & Operation Manual page 24

Tekmarnet 2
Hide thumbs Also See for 403:
Table of Contents

Advertisement

DHW MODE 3 - DHW in Primary / Secondary no
Priority
When a DHW Call is present, the DHW pump and the boiler
system pump are operated. Boiler temperature zones can
turn on if required.
DHW MODE 4 - DHW in Primary / Secondary with
Priority
When a DHW Call is present, the DHW pump and the
boiler system pump are operated. All boiler temperature
zones are shut off through tekmarNet
achieve DHW priority.
DHW Mode 5 - DHW in Near Boiler Piping with
Priority
DHW Mode 5 requires that a DHW sensor be located on
the boiler outlet pipe and a DHW call from an aquastat
inside the DHW tank. The aquastat operates the DHW
tank temperature while the DHW sensor is used to control
the boiler temperature delivered to the DHW indirect heat
exchanger.
When a DHW Call is present, the DHW pump is activated.
The boiler system pump and all boiler temperature zones
are shut off through tekmarNet
DHW priority.
It is assumed that the DHW pump will provide adequate
flow through the heat exchanger and the boiler.
DHW Priority Override -- ----- - ---- ----- ---- - - -- -
To prevent the building from cooling off too much or the
possibility of a potential freeze up during DHW priority,
the control limits the amount of time for DHW priority
during cold weather. During warm weather the DHW
priority is 120 minutes. During cold weather the DHW
priority is 15 minutes. Once the allowed time for priority
has elapsed, the control overrides the DHW priority and
resumes space heating for 15 minutes. It will then revert
back to DHW Priority and repeat.
DHW Post Purge -- -- - ------ ---- - --- --- -- - -- - --
-- -- ------ ----- ---- ----- -- - - - -
After the DHW Call is removed, the control performs a purge
on the boiler. The control shuts off the boiler and continues
to operate the DHW pump and the Boiler System pump if
applicable. This purges the residual heat from the boiler
into the DHW tank. The control continues this purge for a
maximum of two minutes. The control also stops the purge
if the boiler supply temperature drops below the current
boiler target temperature.
© 2011
D 403 - 07/11
®
communication to
®
communication to achieve
------ ----- ---- ----- - - - - - -
DHW
Sensor
DHW Priority Override Time
Decreasing Outdoor Air Temperature
24 of 32
DHW Mode = 3
Zone
Pump
ON
DHW
Or
Pump
OFF
ON
Boiler System
Pump
ON
DHW Mode = 4
Zone
Pump
DHW
OFF
Pump
ON
Boiler System
Pump
ON
DHW Mode = 5
DHW
Pump
ON
Boiler
Sensor
Boiler
Boiler
System Pump
Pump
OFF
OFF
Zone
Pump
OFF