20. AUX2MODE
SCENE:01
SCENE>01
SCENE>06
SCENE>LS
21. LOADSHED
A01<C01
A02<C01
A02>C01
A02>C06
A02>C06 *
A02<C06 *
24
Set the auxiliary input 2 mode to activate a selected scene or load shed.
The auxiliary dry-contact input can be set to activate 1 of the 6 backup scenes, or set
for load shed mode (LS). When the auxiliary input is configured to activate a scene,
scene mode (SCENEMOD) must be enabled for the selected scene to be activated.
Refer to menu item SCENEMOD on page 23 for further details. When the auxiliary
input is configured for load shed mode, dimmers channels selected within the load
shed (LOADSHED) menu are disabled (turned off). Refer to menu item LOADSHED
on page XX for further details.
When both auxiliary inputs are configured to activate a scene, the last action takes
precedence, meaning the last contact sensed activates the selected preset.
Displays the mode setting for the auxiliary input.
Press EXECUTE to enter the menu and edit the mode.
Press MENU (
) to select the desired scene to activate from 01 to 06.
Press MENU (
) to set the auxiliary input to load shed mode (LS).
Press ESCAPE to exit the menu and save the desired mode.
Press RESET to exit the menu without saving.
The menu will automatically timeout after 2 minutes of inactivity and save.
Select dimmers to be disabled (turned off) by the auxiliary inputs.
Load shed is used as a power management interface to building management
systems (BMS). Contact closure devices such as a photocell or maintained switch
contact may be used to trigger the auxiliary input.
Within this menu, dimmer channels are selected and patched to each of the auxiliary
inputs. When the auxiliary input is activated (maintained connection between the
auxiliary input and common), the selected dimmer channel outputs are disabled
(turned off).
Displays the auxiliary input (A01) and dimmer channel (C01).
Press MENU (
) to select the desired auxiliary input 01 or 02 to patch.
Press EXECUTE to toggle the pointer (< >) to select the dimmer channel.
Press MENU (
) to select the desired dimmer channel from 01 to 06.
Press EXECUTE to flag (*) and patch the dimmer channel to the auxiliary input.
Press ESCAPE to toggle the pointer (< >) to select another analog input.
Press ESCAPE to exit the menu and save the desired analog patches.
Press RESET to exit the menu without saving.
The menu will automatically timeout after 5 minutes of inactivity and save.
NOTE: For this menu to function, the auxiliary input (AUX1MODE and/or
AUX2MODE) must be set for load shed mode (XX).