Mitsubishi Electric Mr.Slim PUHZ-RP35VHA2 Service Manual page 42

Split-type, heat pump air conditioners
Hide thumbs Also See for Mr.Slim PUHZ-RP35VHA2:
Table of Contents

Advertisement

Error Code Meaning of error code and detection method
Abnormality of remote controller
control board
1 Abnormal if data cannot be normally
E1
read from the nonvolatile memory of the
or
remote controller control board.
E2
(Error code: E1)
2 Abnormal if the clock function of remote
controller cannot be normally operated.
(Error code: E2)
Remote controller transmission
error(E3)/signal receiving error(E5)
1 Abnormal if remote controller could not
find blank of transmission path for six
seconds and could not transmit.
(Error code: E3)
2 Remote controller receives transmitted
data at the same time, compares the
data, and when detecting it, judges
E3
different data to be abnormal 30
or
continuous times. (Error code: E3)
E5
1 Abnormal if indoor controller board could
not find blank of transmission path.
(Error code: E5)
2 Indoor controller board receives trans-
mitted data at the same time, compares
the data,and when detecting it, judges
different data to be abnormal 30
continuous times. (Error code: E5)
Indoor/outdoor unit communication
error (Signal receiving error)
(Outdoor unit)
(1) Abnormal if outdoor controller circuit
E8
board could not receive anything
(6840)
normally for three minutes.
Indoor/outdoor unit communication
error (Transmitting error) (Outdoor unit)
(1) Abnormal if "0" receiving is detected 30
E9
times continuously though outdoor con-
troller circuit board has transmitted "1".
(6841)
(2) Abnormal if outdoor controller circuit
board could not find blank of transmission
path for three minutes.
Non defined error code
This code is displayed when non defined
EF
error code is received.
(6607
or
6608)
Serial communication error
1.Abnormal if serial communication
between outdoor controller circuit
board and outdoor power circuit board
is defective.
Ed
(0403)
2. Abnormal if communication between
outdoor controller circuit board and
M-NET board is not available.
Case
1 Defective remote controller.
1 Two remote controller are set
as "main."
(In case of 2 remote con-
trollers)
2 Remote controller is connected
with two indoor units or more.
3 Repetition of refrigerant
address.
4 Defective transmitting receiving
circuit of remote controller.
5 Defective transmitting receiving
circuit of indoor controller
board.
6 Noise has entered into trans-
mission wire of remote con-
troller.
1 Contact failure of indoor/out-
door unit connecting wire.
2 Defective communication circuit
of outdoor controller circuit board.
3 Defective communication cir-
cuit of indoor controller board
4 Noise has entered into indoor/
outdoor unit connecting wire.
1 Indoor/ outdoor unit connecting
wire has contact failure.
2 Defective communication circuit
of outdoor controller circuit board.
3 Noise has entered power supply.
4 Noise has entered indoor/ out-
door unit connecting wire.
1 Noise has entered transmis-
sion wire of remote controller.
2 Noise has entered indoor/ out-
door unit connecting wire.
3 Outdoor unit is not a series of
power-inverter.
4 Model name of remote con-
troller is PAR-S25A.
1 Breaking of wire or contact
failure of connector CN2
between the outdoor controller
circuit board and the outdoor
power circuit board.
2 Breaking of wire or contact
failure of connector CN4
between the outdoor controller
circuit board and the outdoor
power circuit board.
3 Defective communication circuit
of outdoor power circuit board
4 Defective communication circuit
of outdoor controller circuit board
for outdoor power circuit board
1 Breaking of wire or contact
failure of connector between
outdoor controller circuit board
and M-NET board
2 Contact failure of M-NET board
power supply line
3 Noise has entered into M-NET
transmission wire.
42
Judgment and action
1 Replace remote controller.
1 Set a remote controller to main, and the
other to sub.
2 Remote controller is connected with only one
indoor unit.
3 The address changes to a separate setting.
4~6 Diagnose remote controller.
a) When "RC OK"is displayed, remote con-
trollers have no problem.
Put the power off,and on again to check.
When becoming abnormal again, replace
indoor controller board.
b)When "RC NG"is displayed, replace
remote controller.
c)When "RC E3"or "ERC 00-66"is displayed,
noise may be causing abnormality.
1 Check disconnection or looseness of indoor/
outdoor unit connecting wire of indoor or out-
door units.
2~4 Put the power off, and on again to check.
Replace indoor controller board or outdoor
controller circuit board if abnormality is
displayed again.
1 Check disconnection or looseness of
indoor/outdoor unit connecting wire.
2~4 Put the power off, and on again to check.
Replace outdoor controller circuit board if
abnormality is displayed again.
12 Put the power off, and on again to check.
Replace indoor controller board or outdoor
controller circuit board if abnormality is
displayed again.
3 Replace outdoor unit with power-inverter type
outdoor unit.
4 Replace remote controller with MA remote
controller.
12 Check connection of each connector CN2
and CN4 between the outdoor controller
circuit board and the outdoor power circuit
board.
3 Replace outdoor power circuit board.
4 Replace outdoor controller circuit board.
1 Check disconnection, looseness, or breaking of
connection wire between outdoor controller cir-
cuit board (CNMNT) and M-NET board (CN5).
2 Check disconnection, looseness, or breaking of
connection wire between outdoor controller cir-
cuit board(CNMNT) and M-NET board (CND).
3 Check M-NET transmission wiring method.