Mitsubishi Electric Mr.Slim PUHZ-RP35VHA2 Service Manual page 104

Split-type, heat pump air conditioners
Hide thumbs Also See for Mr.Slim PUHZ-RP35VHA2:
Table of Contents

Advertisement

13-2.GUIDE FOR OPERATION CONDITION
Inspection item
Breaker
Terminal block
Outdoor Unit
Indoor Unit
(Insulation resistance)
(Voltage)
1 Accumulated operating time
Com-
2 Number of ON/OFF times
pressor
3 Current
4 Refrigerant/heat exchanger temperature COOL
5 Refrigerant/discharge temperature COOL
6 Air/outside air temperature
(Air/discharge temperature)
Appearance
Heat exchanger
Sound/vibration
7
Air/intake air temperature
(Air/discharge temperature)
8
Refrigerant/heat exchanger temperature COOL
9
Filter operating time*
Decorative panel
Filter
Fan
Heat exchanger
Sound/vibration
* The filter operating time is the time that has elapsed since the filter was reset.
Area
Check item
Normal
Normal operation state
Filter inspection
Filter may be clogged. *1
Inspection A
Performance has dropped. Detailed in-
spection is necessary.
Inspection B
Refrigerant amount is dropping.
Inspection C
Filter or indoor heat exchanger may be
clogged.
* The above judgement is just guide based on Japanese standard
conditions.
It may be changed depending on the indoor and outdoor temperature.
Result
Good
Retightened
Good
Retightened
Good
Retightened
M"
V
Time
Times
A
: HEAT
:
: HEAT
:
COOL
: HEAT
:
COOL
: HEAT
:
Good
Cleaning required
Good
Cleaning required
None
Present
COOL
: HEAT
:
COOL
: HEAT
:
: HEAT
:
Time
Good
Cleaning required
Good
Cleaning required
Good
Cleaning required
Good
Cleaning required
None
Present
Judgment
Cool
Heat
Check Points
Enter the temperature differences between
the graph given below.
Operation state is determined according to the plotted areas on
the graph.
For data measurements, set the fan speed to "Hi" before activat-
ing maintenance mode.
Classification
Inspection
Is "D000" displayed stably on the remote
controller?
5
Temperature
(
Discharge temperature) – (
difference
heat exchanger temperature)
7
(
Indoor intake air temperature) – (
Indoor heat exchanger temperature)
Inspection
Is "D000" displayed stably on the remote
controller?
5
Temperature
(
Discharge temperature) – (
difference
heat exchanger temperature)
8
(
Indoor heat exchanger temperature) –
7
(
Indoor intake air temperature)
* Fixed Hz operation may not be possible under the following tempera-
ture ranges.
A)In cool mode, outdoor intake air temperature is 40 : or higher or
indoor intake air temperature is 23 : or lower
B)In heat mode, outdoor intake air temperature is 20 : or higher or
indoor intake air temperature is 25 : or lower
* If the air conditioner is operated at a temperature range other than the
ones above but operation is not stabilized after 30 minutes or more have
elapsed, carry out inspection.
* In heat mode, the operation state may vary due to frost forming on the
outdoor heat exchanger.
Cool mode
:
45
40
Inspection C
35
30
25
Filter inspection
20
Normal
15
Inspection B
10
Inspection A
5
0 10
20 30 40 50 60 70 80
5
4
[
Discharge temperature] – [
heat exchanger temperature)
104
5
4
7
,
,
and
Item
Result
Stable Unstable
4
Outdoor
8
Stable Unstable
8
Indoor
Heat mode
:
45
Inspection C
40
Filter inspection
35
30
25
Normal
20
15
Inspection B
10
Inspection A
5
:
0 10
20 30 40 50 60 70 80
5
Outdoor
[
Discharge temperature] – [
heat exchanger temperature)
8
into
:
:
:
:
:
8
Indoor