OPERATING PROCEDURE
10. Removing the bypass valve
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove the electrical parts box. (See photo 3.)
(4) Remove 3 right side panel fixing screws (5
rear of the unit and remove the right side panel.
(5) Remove the bypass valve solenoid coil. (See photo 7.).
(6) Collect the refrigerant.
(7) Remove the welded part of bypass valve.
Note 1: Collect refrigerant without spreading it in the air.
Note 2: The welded part can be removed easily by
removing the right side panel.
11. Removing the high pressure switch (63H)
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove the electrical parts box. (See photo 3.)
(4) Remove 3 right side panel fixing screws (5
rear of the unit and remove the right side panel.
(5) Pull out the lead wire of high pressure switch.
(6) Collect the refrigerant.
(7) Remove the welded part of high pressure switch.
Note 1: Collect refrigerant without spreading it in the air.
Note 2: The welded part can be removed easily by
removing the right side panel.
Note 3: When installing the high pressure switch, cover it
with a wet cloth to prevent it from heating (100°C
or more), then braze the pipes so that the inside
of pipes are not oxidized.
12. Removing the reactor (ACL)
(1) Remove the service panel. (See figure 1.)
(2) Remove the top panel. (See figure 1.)
(3) Remove the electrical parts box. (See photo 3.)
(4) Remove 3 reactor fixing screws (4
reactor.
w The reactor is attached to the rear of the electrical parts box.
Photo 9
Solenoid valve coil
<Bypass valve>
(SV)
10) in the
Bypass
valve
Linear
expansion
valve
Photo 10
10) in the
Photo 11
16) and remove the
115
PHOTOS
Linear expansion
valve coil (LEV B)
Solenoid valve coil
<Four-way valve>
(21S4)
Lead wire of
High pressure switch (63H)
high pressure switch
Reactor fixing screw
Reactor fixing screws
Linear expansion
valve coil (LEV A)
Linear
expansion
valve
Four-way
Thermistor
valve
<Outdoor pipe>
(TH33)
Reactor
(ACL)
Electrical parts box

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents