OPERATING PROCEDURE
8. Removing the four-way valve
(1) Remove the service panel. (See photo 2.)
(2) Remove the top panel. (See photo 1.)
(3) Remove the front panel. (See photo 1.)
(4) Remove the back panel. (See photo 1.)
(5) Remove the electrical parts box. (See photo 5.)
(6) Remove the solenoid valve coil <Four-way valve>
(See photo 8.)
(7) Collect the refrigerant.
(8) Remove the welded part of four-way valve.
Note 1: Collect refrigerant without spreading it in the air.
Note 2: The welded part can be removed easily by remov-
ing the right side panel.
Note 3: When installing the four-way valve, cover it with a
we cloth to prevent it from heating (120°C or more),
then braze the pipes so that the inside of pipes
are not oxidized.
9. Removing linear expansion valve
(1) Remove the service panel. (See photo 2.)
(2) Remove the top panel. (See photo 1.)
(3) Remove the front panel. (See photo 1.)
(4) Remove the back panel. (See photo 1.)
(5) Remove the electrical parts box. (See photo 5.)
(6) Remove the linear expansion valve coil . (See photo 8.)
(7) Collect the refrigerant.
(8) Remove the welded part of linear expansion valve.
Note 1: Collect refrigerant without spreading it in the air.
Note 2: The welded part can be removed easily by remov-
ing the back panel.
Note 3: When installing the linear expansion valve, cover
it with a wet cloth to prevent it from heating
(120°C or more), then braze the pipes so that the
inside of pipes are not oxidized.
10. Removing the high pressure switch (63H)
(1) Remove the service panel. (See photo 2.)
(2) Remove the top panel. (See photo 1.)
(3) Remove the front panel. (See photo 1.)
(4) Remove the back panel. (See photo 1.)
(5) Remove the electrical parts box. (See photo 5.)
(6) Pull out the lead wire of high pressure switch.
(7) Collect the refrigerant.
(8) Remove the welded part of high pressure switch.
Note 1: Collect refrigerant without spreading it in the air.
Note 2: The welded part can be removed easily by
removing the back panel.
Note 3: When installing the high pressure switch, cover it
with a wet cloth to prevent it from heating (100°C
or more), then braze the pipes so that the inside
of pipes are not oxidized.
11. Removing the reactor (ACL)
(1) Remove the service panel. (See photo 2.)
(2) Remove the top panel. (See photo 1.)
(3) Remove the front panel. (See photo 1.)
(4) Remove the back panel. (See photo 1.)
(5) Remove 3 reactor fixing screws (4
reactor.
w The reactor is attached to the rear of the electrical parts box.
Photo 10
Photo 11
Photo 12
20) and remove the
110
PHOTOS
Linear expansion
valve coil (LEV A)
Linear expansion
valve coil (LEV B)
Linear expansion valve
High pressure
switch (63H)
Charge plug
Reactor fixing screw
Reactor fixing screws
solenoid valve coil
<Four-way valve>
(21S4)
Four-way
valve
solenoid valve coil
<Four-way valve>
fixing screw
Reactor
(ACL)
Electrical
parts box