Displaying Pv/Sv Status; Pv And Sv Status Display Functions - Omron E5CN User Manual

Digital temperature controllers
Hide thumbs Also See for E5CN:
Table of Contents

Advertisement

Displaying PV/SV Status

Operating Procedure
Initial Setting Level
Input Type
in-t
5
Initial Setting Level
Move to Ad-
amov
vanced Function
Setting Level
-169
Advanced Function Setting Level
Parameter
init
Initialization
off
Control Output
ra1
1 ON/OFF
Count Alarm
0
Set Value
Control Output
ra1
1 ON/OFF
Count Alarm
10
Set Value
Initial Setting Level
Input Type
in-t
5
Operation Level
C
25
alm
100

4-21 Displaying PV/SV Status

4-21-1 PV and SV Status Display Functions

PV Status Display
Function
130
This procedure sets the Control Output 1 ON/OFF Alarm Setting parameter to
10 (1,000 times).
1. Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
2. Select the Move to Advanced Function Setting Level parameter by press-
ing the M Key.
3. Use the D Key to enter the password (" − 169"). It is possible to move to
the advanced function setting level by either pressing the M Key or wait-
ing two seconds without pressing any key.
4. Press the M Key to select the Control Output 1 ON/OFF Count Alarm Set
Value parameter.
5. Use the U Key to set the parameter to 10.
6. Press the O Key for at least one second to move to the initial setting lev-
el.
7. Press the O Key for at least one second to move to the operation level.
The PV in the PV/SP, PV, or PV/Manual MV Display and the control and alarm
status specified for the PV status display function are alternately displayed in
0.5-s cycles.
Set value
OFF
Manual
Stop
Alarm 1
Alarm 2
Symbol
off
No PV status display
manu
MANU is alternately displayed during
manual control.
stop
STOP is alternately displayed while oper-
ation is stopped.
alm1
ALM1 is alternately displayed during
Alarm 1 status.
alm2
ALM2 is alternately displayed during
Alarm 2 status.
Section 4-21
Function

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5cn-uE5anE5en

Table of Contents