Initial Setting Level
ev-m
Number of Multi-SP Uses
Function
Setting
196
• Multi-SP is a function for setting set points 0 to 3 in advance, and switch-
ing between these set points using a combination of event input ON/OFF
signals.
• The Number of Multi-SP Uses parameter is used to switch between using
two and four preset set points.
Setting range
Default
0 to 2
1
• Whether the Event Input Assignments 1 and 2 parameters are displayed
or hidden is determined by the Number of Multi-SP Uses parameter set-
ting.
Controllers with Event Inputs 1 and 2 (Two Event Inputs)
Event input assignment 1
Number of multi-
0
Displayed (Multi-SP not used).
SP uses
1
Hidden (Multi-SP, 2 points).
2
Hidden (Multi-SP, 4 points).
The following tables show the relationships between ON/OFF combinations of
event inputs 1 and 2 and selected set points.
Number of Multi-SP Uses: 1:
Even input 1
OFF
Set point 0
ON
Set point 1
Number of Multi-SP Uses: 2
Even input 1
OFF
OFF
ON
OFF
OFF
ON
ON
ON
• The following table shows the functions assigned when an Event Input
Assignment (1 or 2) is displayed.
Setting
none
None
stop
RUN/STOP
manu
Auto/Manual Switch
prst
Program start (See note 1.)
drs
Invert Direct/Reverse Operation
at-2
100% AT Execute/Cancel
at-1
40% AT Execute/Cancel (See note 2.)
wtpt
Setting Change Enable/Disable
lat
Alarm Latch Cancel
An event input must be assigned.
Displayed (Event input 2 not
used as multi-SP switch).
Selected set point
Even input 2
Set point 0
Set point 1
Set point 2
Set point 3
Function
Section 5-7
Event input assignment 2
Selected set point