Continuous - Mitsubishi Electric Mr.SLIM PUH-P1VGAA Technical & Service Manual

Split-type, heat pump air conditioners split-type, air conditioners
Hide thumbs Also See for Mr.SLIM PUH-P1VGAA:
Table of Contents

Advertisement

Error Code Meaning of error code and detection method
Abnormal high pressure (High-pressure
switch 63H worked)
Abnormal if high-pressure switch 63H
worked (more than 3.24 MPa) during com-
pressor operation.
63H: High-pressure switch
Use current sensor to detect work or
return of 63H.
U1
(1302)
Abnormal low current or open phase
• An extreme degradation of current value
causes abnormal stop.
• Abnormal if current detected phase (V-
phase) is open phase after first compres-
sor start-up after supplying the power by
three phase power supply model.
• When compressor is operating, compres-
sor is suspended under the following
condition: and when current detector
(CT) detects a current, which is lower
than the detected current specified in the
table below, under the following condi-
tion:
<Condition>
1 For PUH-P1V and PU/PUH-P1.6 ~ P4V
Current detector (CT) has detected a
current, which is lower than the detected
current specified in the table below, for
U1
0.7-0.8 second.
2 For PU/PUH-P1.6 ~ P6Y
Current detector (CT) has detected a
current, which is lower than the detected
current specified in the table below, for
0.4-0.5 second.
Model
Detected current
P1V
1.0
P1.6V
1.3
P1.6Y
1.0
P2V
1.6
P2Y
1.0
P2.5V
1.8
P2.5Y
1.0
Abnormal high discharging temperature
Abnormal if discharging temperature ther-
mistor (TH4) exceeds following tempera-
ture during compressor operation.
U2
Normal operation: 125: or more for three
(1102)
During defrosting: 135:
1 Short cycle of indoor unit
2 Clogged filter of indoor unit
3 Decreased airflow caused by
dirt of indoor fan
4 Dirt of indoor heat exchanger
5 Locked indoor fan motor
6 Malfunction of indoor fan
motor
7 Defective operation of stop
valve (Not full open)
8 Clogged or broken pipe
9 Locked outdoor fan motor
0 Malfunction of outdoor fan
motor
1 Short cycle of outdoor unit
2 Dirt of outdoor heat exchanger
3 Disconnection or contact failure
of 63H connection
4 Defective outdoor controller
board
5 Defective action of liner expan-
sion valve
6 Refrigerant overcharge
1 Shortage of refrigerant
2 Abnormal pressure degrada-
tion by pomp down operation
3 V-phased open phase of com-
pressor
4 Abnormal compressor
Not abnormal if V is instantly
displayed when the main
power is put off.
[A]
Model
Detected current
P3V
2.4
P3Y
1.0
P4V
1.0
P4Y
1.0
P5Y
1.5
P6Y
1.7
1 Over-heated compressor oper-
ation caused by shortage of
refrigerant
2 Defective operation of stop
valve
3 Defective thermistor
minutes continuously or
4 Defective outdoor controller
135:
board
5 Defective action of linear
expansion valve
Case
39
Judgment and action
1-6 Check indoor unit and repair defectives.
7 Check full open stop valve.
8 Check piping and repair defectives.
9-2 Check indoor unit and repair defectives.
3,4 Put the power off and check UH display
when the power is put again.
Follow the UH display if UH is displayed.
5 Check linear expansion valve.
Refer to 11-3.
6 Replace refrigerant.
1 Check if refrigerant pressure is not degraded.
2 Check current of compressor operation when
abnormality occurred.
3 Check wiring of compressor.
4 Check or replace compressor.
1 Check intake super heat.
Check leakage of refrigerant.
Charge refrigerant.
2 Check if stop valve is full open.
34 Put the power off and check if U3 is
displayed when the power is put again.
When U3 is displayed, refer to "Judgement
and action" for U3.
5 Check linear expansion valve.
Refer to 11-3.